Checking Procedure Of Error History - Daikin BRC1E52B7 Installation Manual

Wired remote controller
Hide thumbs Also See for BRC1E52B7:
Table of Contents

Advertisement

Remote controller display
Display of "Checking the connection
Please stand by" is turned on. *
* Though "Checking the connection
Please stand by" is displayed for 90 seconds at maximum after power-on, this does not mean a failure.
(Determine after 90 seconds.)

8. Checking procedure of Error History

8-1
Press and hold Cancel button for
4 seconds or longer in the basic
screen. Service Settings menu is
displayed.
8-2
Select
Error History
Settings menu, and press Menu/Enter
button. The Error History menu screen
is displayed.
8-3
Select
RC Error History
History menu, and press Menu/Enter
button.
Error codes and unit No. can be
confirmed in the error record display
screen.
8-4
In the Error History, 10 items from the
latest are displayed in order.
8-5
Press Cancel button in the Error
History display screen 3 times.
The basic screen returns.
Installation manual
19
No display
in the Service
in the Error
● Power outage, power voltage error or open-phase
● Wrong wiring (between indoor and outdoor units)
● Indoor PC-board assembly failure
● Remote controller wiring disconnection
● Remote controller failure
● Fuse blown (outdoor unit)
● Indoor PC-board assembly failure
● Wrong wiring (between indoor and outdoor units)
8-1
<Basic screen>
<Service Settings menu screen>
8-2
Service Settings
Indoor unit AirNet Address
Outdoor unit AirNet Address
Error History
Indoor Unit Status
Outdoor Unit Status
Forced Fan ON
Return
Setting
8-3
Error History
RC Error History
Indoor unit Error History
Return
Setting
8-4
RC Error History
8-5
Unit Error
Date
01 –– ––
––
/
––
02 –– ––
––
/
––
03 –– ––
––
/
––
04 –– ––
––
/
––
Return
Unit No.
Latest record
Description
1/3
Press Menu/Enter button.
2/2
Press Menu/Enter button.
1/3
Time
/
–– ––:––
/
–– ––:––
/
–– ––:––
/
–– ––:––
BRC1E52B7
4PW72364-1 – 11.2011