AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 40A.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input
and output connectors.
WARNING! All wiring must be performed by the qualified personnel.
WARNING! It's necessary to connect AC input N wire. Otherwise, the inverter will NOT be able to detect
AC input.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input
connection. To reduce risk of injury, please use the recommended cable size as below.
Suggested cable requirement for AC wires
Model
HYBRID LV 6048
There are three applications for different AC input as shown in the figure below. For phase angle operation,
please refer to LCD #28
L1
Grid
N
0V
connection
L2
When the phase angle between L1 and L2 is 120°.
L1
Grid
N
208V
connection
L2
When the phase angle between L1 and L2 is 180°.
L1
Grid
N
240V
connection
L2
Gauge
10 AWG
When the phase angle between L1 and L2 is 0°.
L1
120V
N
120V
L2
L1
120V
N
120V
L2
L1
120V
N
120V
L2
Torque Value
1.4~ 1.6Nm
L1
MLV 6KW
N
L2
L1
MLV 6KW
N
L2
L1
MLV 6KW
N
L2
7
L1
120V
N
0V
120V
L2
L1
120V
Load
N
208V
Output
120V
L2
L1
120V
Load
N
240V
Output
120V
L2
Load
Output