Troubleshooting
Symptom
Possible Cause
System display only: AGS
function does not work if
Advanced
another valid input is present.
Generator Start
(AGS) fails to
activate when
System display is not present. AGS programming is located in the system display and
conditions are met
(or starts when
conditions are not
Other A
met).
operation.
AGS or Gen Alert
The inverter's G
functions start the
use and the input priority is
set to GRID.
generator, but the
inverter does not
accept the power
and shuts off the
generator again.
Module Select
The GS8048A uses two high-frequency H-Bridge FET modules. The dual design allows half the
inverter to shut down for lower idle consumption. Normally this is automatically selected. If one
module fails or if troubleshooting is otherwise needed, the module selection can be performed
manually. The GS8048A can be directed to use a single, specified module (left or right), or it
can be directed to turn on both modules continuously. This procedure should only be performed
if directed by OutBack Technical Support.
Although the GS4048A has only a single module, this command is still available. The default
setting is Left, which is the location of the module. Do not change this setting in the GS4048A.
The Module Select menu options are displayed as part of Table 17, which begins on page 63.
50
Table 5 Troubleshooting
Possible Remedy
Check both inputs for a second AC source (utility grid). If the
inverter detects an acceptable AC source, it will not allow
AGS. This is true even if it is internally disconnected from the
source (due to HBX mode, Mini Grid mode, or similar
programming).
cannot function if the system display is removed.
functions are in
Gen Alert or another A
UX
generator using the wrong criteria. Make sure all other A
functions are disabled.
input is in
If the input priority is set to GRID and the G
RID
energized, an automatically controlled generator will shut
down. This could indicate that the generator has been wired
to the G
is active on the G
G
when automatically controlling a generator.
Either the G
controlling a generator.
function may try to start or stop the
UX
input, or it could indicate that another AC source
RID
input while the generator is using the
RID
input. The G
input must be the only terminals in use
EN
EN
or G
input can be used when manually
RID
EN
UX
terminals are
RID
900-0161-01-01 Rev B