3.6. Access to the VF-AS1/PS1 parameter

When access to the VF-AS1/PS1 parameter, set "1" to the PNU. The communication
number of the inverter parameter is set to the subindex IND.
Refer to the inverter instruction manual about the communication number and unit.
3.6.1.

Examples of reading or changing the VF-AS1/PS1 parameter

3.6.1.1. Example 1. Reading the basic parameter (cmod (command mode selection))
AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0x0003 (cmod communication number)
PKE
0
Requirement
PKW
PKE
60
Response (Value: 0x0001 = Operation panel))
40
3.6.1.2. Example 2. Reading the extended parameter (f219 (RX input point 2 frequency))
AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0x0219 (f219 communication number)
PKE
0
Requirement
PKW
PKE
60
Response (Value: 0x1770 (= 6000 -> 60.00Hz
40
* "0x1770" as reading value of "RX input point 2 frequency" is
Since the unit of "RX input point 2 frequency" is 0.01Hz, set the following value.
1
1
0
0
6
IND
01
00
03
01
00
03
1
1
0
0
6
IND
01
02
19
01
02
19
0x1770 = 6000 (decimal number)
6000×0.01 = 60.00Hz
0
0
0
0
0
PWE
00
00
00
00
00
00
0
0
0
0
0
PWE
00
00
00
*
))
00
00
17
- 17 -
E6581343 ③
0
0
0
0
0
0
PZD
00
・・・
・・・
01
・・・
・・・
0
0
0
0
0
0
PZD
00
・・・
・・・
70
・・・
・・・
0
1
1
0
1
1