Communications-Related Parameters Of The Vf-As1 - Toshiba TOSVERT VF-AS1 Option Instruction Manual

Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

5. Communications-related parameters of the VF-AS1

On the network, the VF-AS1 (including the PDP002Z) serves as a slave device. Using the
parameters listed below, set the slave device on the network and its mode of operation.
The GSD files used to configure the PDP002Z can be downloaded from the Toshiba
Schneider Inverter web site.
http://www.inverter.co.jp/product/inv/vfas1/pdp/
Parameter
Function
f830*
Communication option
setting 1
(PPO TYPE)
f851
Inverter operation at the
communications
loss action
(Network wire breaks)
f852
Preset speed
operation
f853
Monitoring of
communication device
station address
f854**
Monitoring of
communications
device's baud rate
* When the parameters are changed, the power must be cycled to the VF-AS1 for the
changes to take effect.
** The baud rate of the PDP002Z is automatically set by configuration a baud rate for the
master.
0: None
1: PPO TYPE 1
2: PPO TYPE 2
3: PPO TYPE 3
4: PPO TYPE 4
0: Stop and break of connection
1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
5: Preset speed operation command
(Operating at the preset speed operation frequency
set with f852)
0: None
selection
1 to 15: Preset speed
Displays the station address assigned with the
DIP switch.
0 to 125
Displays the network communication speed set
with the DIP switch.
0:
12 Mbit/s
1:
6 Mbit/s
2:
3 Mbit/s
3:
1.5 Mbit/s
4:
500 kbit/s
5:
187.5 kbit/s
9 3.75 kbit/s
6:
7:
45.45 kbit/s
8:
19.2 kbit/s
9:
9.6 kbit/s
255:
Disabled
- 13 -
Adjustment range
E6581279
Default setting
0
0
0
1
0

Advertisement

Table of Contents
loading