Chapter 1: Introduction
Thank you for purchasing this power protection product. It has been designed
and manufactured to provide many years of trouble free service. Please read
this manual before installing your Encompass On-Line Series UPS, models
EC1000RT2U, EC1500RT2U, EC2000RT2U, EC3000RT2U as it provides im-
portant information that should be followed during the installation and the main-
tenance of the UPS system allowing you to correctly set up your system for
the maximum safety and performance. Included is information on customer
support and factory service, if it is required. If you experience a problem with
the UPS system please refer to the Troubleshooting guide in this manual to
correct the problem or collect enough information so that the Technical Sup-
port Department can assist you.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
CONSIGNES DE SÉCURITÉ IMPORTANTES
SAUVEGARDEZ CES CONSIGNES!
Veuillez lire ce manuel avant l'installation de l'onduleur modèles EC1000RT2U,
EC1500RT2U, EC2000RT2U, EC3000RT2U. Il contient de l'information
importante qui doit être respectée au cours de l'installation et de l'entretien de
l'onduleur et des batteries. Cette information vous permettra de correctement
installer le système pour atteindre son rendement maximum en toute sécurité.
CAUTION! The maximum ambient operating temperature for this UPS series
is 40°C ("0 ~ 40°C" for Ambient Operation).
The external vents and openings on the UPS are provided for ventilation.
To ensure reliable operation of the UPS and to protect the UPS from over-
heating, these vents and openings must not be blocked or covered. Do not
insert any object into any of the vents or openings that may hinder the ve-
ntilation.
Install the UPS system in a well ventilated area, away from excess moistu-
re, heat, dust, flammable gas or explosives.
Leave adequate space (at least 20cm) in the front and at the rear of the
UPS system for proper ventilation.
Do not mount the UPS system with its front or rear panel facing down at
any angle.
 Before usage, you must allow the UPS system to adjust to room temper-
ature (20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture
condensing inside the UPS.
2
CAUTION! This UPS series is ONLY intended to be installed in an indoor
temperature controlled environment that is free of conductive contaminants.
This UPS series is not intended for use in a computer room as defined in the
Standard for the Protection of Electronic Computer/Data Processing Equip-
ment ANSI/NFPA 75.
CAUTION!
Connect the UPS to a two pole, three wire grounded AC wall
outlet. The receptacle must be connected to the appropriate branch protec-
tion (circuit breaker or fuse). Connection to any other type of receptacle may
result in a shock hazard and violate local electrical codes. Do not plug the
UPS into extension cords, adapter plugs or surge strips.
CAUTION!
To reduce the risk of fire, connect only to a utility powered
circuit provided with 20 / 30 amperes maximum branch circuit over-current
protection in accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION!
To reduce the risk of electrical shock with the installation of this
UPS equipment and the connected equipment, the user must ensure that the
combined sum of the AC leakage current does not exceed 3.5mA.
CAUTION!
To reduce the risk of electrical shock in conditions where the
load equipment grounding cannot be verified, disconnect the UPS from the
AC wall outlet before installing a computer interface cable. Reconnect the
power cord only after all signaling connections are made.
WARNING:
This Uninterruptible Power Supply contains potentially hazard-
ous voltages. Do not attempt to disassemble the UPS beyond the battery
replacement procedure. This UPS contains no user serviceable parts. Re-
pairs and Battery replacement must be performed by QUALIFIED SERVICE
PERSONNEL ONLY.
WARNING: Qualified Service Personnel ONLY must perform the Installa-
tion and Servicing of these UPS systems. MINUTEMAN accepts no liabilities
and is not limited to: injury to the Service Personnel, or damages to; the UPS,
or the connected equipment caused by the incorrect installation or servicing
of the UPS system.
WARNING:
Risk of Electrical Shock. Hazardous live parts inside these
power supplies are energized from the battery even when the AC input is
disconnected.
CAUTION!
DO NOT USE THE MOUNTING BRACKETS TO LIFT THE
UPS. The mounting brackets are ONLY for securing the UPS to the rack.
NOTE: These UPSs are shipped with the batteries disconnected. The batter-
ies must be connected before putting these UPSs into service. Refer to Sec-
tion 3 "Installation" for connecting the batteries.