For Analogue and Digital Interface.
FCC ID
2ACTT-1409
Installation Guide.

Advertisement

Table of Contents
loading

Summary of Contents for Intech Instruments Z-2400-A2 Series

  • Page 1 Z-2400-A2 Series ® Wireless Data Links Using ZIGBEE For Analogue and Digital Interface. FCC ID 2ACTT-1409 Installation Guide.
  • Page 2: Table Of Contents

    Connecting Pulse, Frequency & On/Off State Signals to the Z-2400-A2I & Z-2400-A2O Page 17 Digital Inputs. Z-2400-A2O Current Loop Outputs. Page 18 Z-2400-A2 Series Wiring, Installation and Maintenance. Page 18 Z-2400-A2 Wiring and Installation. Page 18 Z-2400-A2 Commissioning. Page 19 Z-2400-A2 Maintenance.
  • Page 3: Description

    Input Remote Wireless node. 2x Isolated Universal Inputs, 4x Digital I/O.  Z-2400-A2R Repeater node for Wireless Extension. Note: The Z-2400-A2 Series require the XU-USB Programming Key for Software Configuration: USB Programming Key for programming Z-2400-A2 Series using uP Configure Programming software. XU-USB (Rev 1): (Same Key as used for programming XU Series transmitters, 2400-A16, Z-2400-Sleeper, IN-uP4 and uP4-Din.)
  • Page 4: Specifications

    Specifications. Analogue Input 1~2 Specifications. Input Resolution 16 Bits, 50,000 Steps Average (some ranges may differ). Input Isolation 2500Vac for 1 minute between Inputs. Sensor Break RTDs & Thermocouples: Upscale. Broken Link or Other Input Types: Downscale. Voltage Input Specifications: Input Impedance >500KΩ...
  • Page 5: Digital Input 1~4 Specifications

    Digital Input 1~4 Specifications. Frequency Range 0~1Hz. Input Threshold 1.4Vdc. Maximum Amplitude 30Vdc continuous. Open Collector Excitation 3Vdc. Isolation Not isolated to the power supply common. Digital Output 3~4 Specifications. Open-Drain, 30Vdc, 1A Max. (Not isolated to the power supply common.) Relay Output 1~2 Specifications.
  • Page 6: Physical Layout Z-2400-A2 Series

    Physical Layout Z-2400-A2 Series. Side - Standing Side - DIN Rail Mount Front With Standard Antenna Fitted 151mm 102mm 225mm 147mm 120mm Side - DIN Rail Mount With Coax Fitted 24mm 111mm (Including Terminal Connectors.) Front Panel Connections and LEDs.
  • Page 7: Diagnostic Leds

    Diagnostic LEDs. RF Signal Strength LED indication. Each LED corresponds to the measured signal quality levels:  One illuminated LED indicates very weak or no signal.  Two illuminated LED’s indicates low signal level.  Three illuminated LED’s indicates medium signal level. ...
  • Page 8: Power And Zigbee Network Led Indication

    Mesh signals will overlap. You can program the Mesh ID of the Repeater node via the ‘uP Configure’ software. The Input and Output nodes are supplied paired with a unique ID. Programming the Z-2400-A2 Series. uP Configure Software.
  • Page 9: Z-2400-A2 Usb Connection

    Note: uP Configure requires Microsoft .NET 2.0 to Note: An Administrator account or password will be be installed first. If .NET 2.0 is not already installed, required for installation. Contact your IT support for a prompt will advise this so you can install online. this if needed.
  • Page 10: Using The Up Configure Software - Version 1.2.8.0 Or Later

    Using the uP Configure Software - version 1.2.8.0 or later. To run uP Configure, double click on the icon on your desktop. uP Configure Home Screen Configuring the Z-2400-A2O: Starting with your Z-2400-A2O connected to your computer via the XU-USB programming key, Click on the Connect button.
  • Page 11: Configuring The Z-2400-A2I

    Configuring the Z-2400-A2I: The Z-2400-A2I Input node connects to your computer the same as the Z-2400-A2O Output node, via the XU-USB programming key. Click on the Connect button in the uP Configure software to get started. The Overview page also has the same information: node type, Mesh ID and Transmit Power. You’ll also notice a row of tabs across the top left hand side of the screen for setting up the inputs, outputs and setpoints.
  • Page 12 Offset Adjust: Offset adjust is for calibration purposes only, this allows you to fine tune the Display Value of an incoming signal. Filter Time: The filter time can be used to help filter out any electrical noise on the input signals. This can be set in 1 second increments. Linearisation: This brings up a table where you can set your own linearisation values manually.
  • Page 13: Configuring The Z-2400-A2R

    Remember to ALWAYS click the ‘Apply’ button after you change any settings, this will program the new settings to your Z-2400-A2R node. To disconnect the Z-2400-A2R node from your computer, click on Disconnect in the top right corner of the screen. Connecting up the Z-2400-A2 Series. Z-2400-A2 Series Power Supply Connection. Power Supply: 9~36Vdc.
  • Page 14: Z-2400-A2I Analogue Input Connections

    Z-2400-A2I Analogue Input Connections. ALWAYS program the Z-2400-A2I before connecting inputs! Remember to always reset (power off and on) the Z-2400-A2I after programming. CAUTION Risk of electric shock. Dangerous and lethal voltages may be present on the terminal of the device.
  • Page 15: Connecting Voltage Signals To The Z-2400-A2I Analogue Inputs

    Connecting Voltage Signals to the Z-2400-A2I Analogue Inputs. Z-2400-A2I Note 1. Input voltage must not exceed 24Vdc. Note 2. All cables to be screened, and the screens earthed at one end only. mV or V Input mV or V Input Connecting Current Signals to the Z-2400-A2I Analogue Inputs.
  • Page 16: Z-2400-A2I & Z-2400-A2O Digital Input/Output Connections

    Connecting Pulse, Frequency & On/Off State Signals to the Z-2400-A2I Analogue Inputs. Z-2400-A2I PNP Open Collector TTL Input (0~5Vdc max) Z-2400-A2I & Z-2400-A2O Digital Input/Output Connections. The Digital Input/Outputs of the Z-2400-A2I & Z-2400-A2O can transmitted both ways to allow for easy monitoring and control from either end of the wireless link, or a single direction if set to alarm/control mode.
  • Page 17: Connecting To The Z-2400-A2I & Z-2400-A2O Digital Outputs

    Connecting to the Z-2400-A2I & Z-2400-A2O Digital Outputs. The two digital outputs can be used for pulse and frequency into a counter or totaliser. 30Vdc, 1A max. Z-2400-A2I / Z-2400-A2O Instrument Quality 24Vdc Power Supply DI 4 Note 1. Always link the ‘SINK/SRC’ & ‘GND’ terminals. PSW-10-F DI 3 Note 2.
  • Page 18: Z-2400-A2O Current Loop Outputs

    4~20mA Display IN-uP4 4~20mA Z-2400-A2 Series Wiring, Installation and Maintenance. THE Z-2400-A2 NODES ARE TO BE INSTALLED AND SERVICED BY SERVICE PERSONNEL ONLY. NO OPERATOR / USER SERVICEABLE PARTS. BEFORE YOU BEGIN WIRING: Ensure that all programming is carried out BEFORE any wiring takes place! All power and signals must be de-energised BEFORE connecting any wiring.
  • Page 19: Z-2400-A2 Commissioning

    Thermocouples: Avoid locating the thermocouple where it will be in a direct flame. Never insert a porcelain or refactory tube suddenly in a hot area. Pre-heat gradually while installing. Locate it where the average temperature will be measured. It should be representative of the mass. If necessary use several thermocouples to obtain the average temperature.
  • Page 20: Troubleshooting

    The ZigBee® system does not offer 100% connectivity, even when all the precautions are taken into account no one can guarantee a good link, as there are many factors that cause problems. With the Z-2400-A2 Series, additional repeaters can be used in between the Input and Output wireless nodes (particularly good when transmitting through solid walls).