5.3
Client Side Node Parameters
Section Title
Nodes
Column Title
Node_Name
Node_ID
Protocol
Port
Node_Inactivity_Timeout*
Example
//
Client Side Nodes
Nodes
Node_Name
, Node_ID
Panel_1
, 2
2
The Notifier Panel must be configured to supervise the port on which the FieldServer is connected. Only use when port
supervision is enabled on the panel.
Function
Provide name for Node
Station address of any physical
Node on network
Specify protocol used
Specify which port the device is
connected to the FieldServer
Used to monitor the connection to
the panel for inactivity.
there be no response from the
panel for the set number
seconds, the FieldServer will mark
2
the node offline.
, Protocol
, Port
, Node_Inactivity_Timeout
, nfs2-nca
,P8
, 15
Page 11 of 23
FS-8700-130 Notifier NCA2-NFS2-3030 Manual
Legal Values
Up to 32 alphanumeric characters
1-240. Set unique Id for standalone
Notifer-3030 Panel
nfs2-nca or nca2 ; nfs2-3030
P1-P8
Should
-, 1-Any value in seconds
(Use a timeout value greater than
of
how often the panel will issue a query
poll.)