5.4.3 Map Descriptor Example: Standard example
This shows the standard Map Descriptor setup for one Node with 1 loop and all 159 modules and 159 detectors installed. This Node also has all
boards, panel and bell circuits
//
// Client Side Map Descriptor
//
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Loop , Data_Type
SMD_N2_Troubles
, DA_SYS_N2
SMD_N2_PANEL
, DA_N2_PANEL
SMD_N2_PANEL_T
, DA_N2_PANEL_T , 0
SMD_N2_BELL_T
, DA_N2_BELL_T
SMD_N2L01D
, DA_N2L01D
SMD_N2L01D_T
, DA_N2L01D_T
SMD_N2L01M
, DA_N2L01M
SMD_N2L01M_T
, DA_N2L01M_T
All Map Descriptors are
Select the array
Passive; waiting for a
for data storage
message from the Notifier
panel.
FS-8700-130 Notifier NCA2-NFS2-3030 Manual
, 0
, Passive , NODE2
, 0
, Passive , NODE2
, Passive , NODE2
, 0
, Passive , NODE2
, 0
, Passive , NODE2
, 0
, Passive , NODE2
, 0
, Passive , NODE2
, 0
, Passive , NODE2
Identify the Loop id for
which this Map
Descriptor will store
data
Page 13 of 23
For Node, Panel and
Bell mapping, the
Loop parameter is
not applicable
, Address , Length
, -
, Node_Trouble
, 1
, -
, Panel
, 1
, -
, Panel_Trouble
, 1
, -
, Bell_Trouble
, 1
, 1
, Detector
, 1
, 1
, Detector_Trouble , 1
, 1
, Module
, 1
, 1
, Module_Trouble
, 1
Specify
Data
Type
, 508
, 1056
Node
, 96
Events
, 4
, 1749
, 159
Loop 1
Events
, 1749
, 159
Specify range,
starting address
and length
Need help?
Do you have a question about the FieldServer FS-8700-130 and is the answer not in the manual?