Lutron Electronics DW-6095 Operation Manual page 52

Table of Contents

Advertisement

B : Operation Instructions:
B-1 : Power on the instrument by pressing POWER KEY,
and then press 1Φ 3Φ KEY to select the 1Φ 3W system,
the selected name of system will be appeared on bottom
left display of screen 2.
B-2 : Connect the line voltage L1, L2 and Vn (Neutral) to
V1, V2 and N terminals of the instrument.
B-3 : Place the conductor of CP-1201(A1), CP-1201(A2)
hook to A1 and A2 as screen 1.
B-4 : Connect the outputs of clamp meter
CP-1201(A1)、CP-1201(A2) to A1 and A2 terminals of
the instrument.
B-5 : The related measuring factors will be appeared on
display, about the instruction of factor please refer
appendix 1 ( 5-16, page 68 ).
screen 2 ( 5-2 )
V 1 :
0.0
V 2 :
0.0
A 1 :
0.00
A 2 :
0.00
Q 1 : - 0.000KVAR
Q 2 : - 0.000KVAR
PΣ :
0.000 KW
PF1:
- 0.00
PFH:
0.00
WH:
0.000 KWH
QH:
0.000 KVARH
CP1201
20A
1Φ 3W
V
V
A
A
SΣ :
0.000 KVA
PF2:
- 0.00
Φ 1:
- 0.0°
SH:
FREQ:
SEC:
P 1 : - 0.000KW
P 2 : - 0.000KW
S 1 :
0.000KVA
S 2 :
0.000KVA
QΣ :
PFΣ :
Φ 2:
0.000 KVAH
50.0 Hz
2
CT:
1
48
0.000 KVAR
0.00
- 0.0°
PT:
1