Active (Real) Power
Range
0.000 to 9.999 KW
10.00 to 99.99 KW
100.0 to 999.9 KW
1.000 to 9.999 MW
* : The resolution is changed according the different ACA range.
Apparent Power
Range
0.000 to 9.999 KVA
10.00 to 99.99 KVA
100.0 to 999.9 KVA
1.000 to 9.999 MVA
* : The resolution is changed according the different ACA range.
Reactive Power
Range
0.000 to 9.999 KVAR
10.00 to 99.99 KVAR
100.0 to 999.9 KVAR
1.000 to 9.999 MVAR
* : The resolution is changed according the different ACA range.
Watt Hour ( Active Power Hour) : WH
Range
0.000 to 9.999 KWH
10.00 to 99.99 KWH
100.0 to 999.9 KWH
1.000 to 9.999 MWH
Resolution
*0.001/0.01/0.1 KW
*0.01/0.1 KW
0.1 KW
0.001 MW
Resolution
*0.001/0.01/0.1KVA
*0.01/0.1 KVA
0.1 KVA
0.001 MVA
Resolution
*0.001/0.01/0.1KVAR
*0.01/0.1 KVAR
0.1 KVAR
0.001 MVAR
Resolution
0.001 KWH
0.01 KWH
0.1 KWH
0.001 MWH
7
Accuracy
± (1%+0.008KW)
± (1%+0.08KW)
± (1%+0.8KW)
± (1%+0.008MW)
Accuracy
± (1%+0.008KVA)
± (1%+0.08KVA)
± (1%+0.8KVA)
± (1%+0.008MVA)
Accuracy
± (1%+0.008 KVAR)
± (1%+0.08 KVAR)
± (1%+0.8 KVAR)
± (1%+0.008 MVAR)
Accuracy
± (2%+0.008 KWH)
± (2%+0.08 KWH)
± (2%+0.8 KWH)
± (2%+0.008 MWH)