BCS Switchgear Inc. Switchgear | Circuit Breakers | Parts | Tech Support S E L - 3 0 0 G G e n e r a t o r R e l a y Quick-Start Installation Guide bcsswitchgear.com | 888.599.0486 Need Help? 888.599.0486...
Page 5
CAUTION: Do not apply reverse polarity dc voltage or ac ATTENTION! N’appliquer pas un voltage CC avec polarité voltage to terminals Z25 and Z26 of SEL-300G Relays rated inversée ou un voltage CA, sur les bornes Z35 et Z26 des for 24/48 Vdc applications.
TABLE OF CONTENTS INTRODUCTION......................1 What This Manual Contains ......................1 To Obtain an SEL-300G Relay Instruction Manual ................ 1 Factory Assistance ........................... 1 Safety Information ........................... 1 RELAY COMMISSIONING PROCEDURE..............2 Introduction............................2 Required Equipment ........................2 Commissioning Procedure ....................... 3 SERIAL PORT COMMAND SUMMARY ...............
Page 8
Figure 19: SEL-300G3 Rear-Panel Drawings for Rack- and Panel-Mount Relays (2U and 3U), Connectorized Version......................30 Figure 20: Jumper, Connector, and Major Component Locations on the SEL-300G Main Board (All Models) ..........................32 Figure 21: Jumper, Connector, and Major Component Locations on the SEL-300G Extra I/O Board(Models 0300G_1, Screw-Terminal Block Version) ............
Procedure section of this guide. To Obtain an SEL-300G Relay Instruction Manual To obtain a copy of the SEL-300G Relay Instruction Manual, simply contact the factory using the instructions below. The SEL-300G Relay Instruction Manual contains additional details on relay operation and settings calculations.
Introduction The procedure below is intended to help you enter settings into an SEL-300G and verify that the relay is properly connected. Steps later in the procedure call for operation of the protected generator at no load, light load, and full load to verify ac connections and take measurements for calculation of 100% stator ground fault protection elements.
Relay Commissioning Procedure Step 1. Ensure that dc power is removed from the SEL-300G dc circuits by opening the appropriate dc breaker or removing dc fuses. Step 2. Verify the accuracy and correctness of the ac and dc connections by performing point-to-point continuity checks on the circuits associated with the SEL-300G Relay.
Page 13
SEL World Wide Web site at http://www.selinc.com. Serial Port 1 on all the SEL-300G models is an EIA-485 port (4-wire). The Serial Port 1 plug-in connector accepts wire size AWG 24 to 12. Strip the wires 0.31 inches (8 mm) and install with a small slotted-tip screwdriver.
ST connectors A corresponding main board jumper must be installed to power the StarComm Modem with +5 Vdc (0.5 A limit) from the SEL-300G. See Figure 20 and Table 11. Data Terminal Equipment Data Communication Equipment Refer to Model Option Table for additional cable choices.
Page 15
9-Pin Female “D” Subconnector “D” Subconnector “D” Subconnector “D” Subconnector Step 9. SEL relays respond to ASCII text commands entered on the Hint relay serial port. PC terminal emulation packages such as For the best display, use ® ® Windows...
Page 16
Failure to change each default password to a private password may allow unauthorized access. SEL shall not be responsible for any damage resulting from unauthorized access. The factory default passwords for Access Levels 1, B, and 2...
Step 12. Verify relay ac connections. Connect the protective relay ac test signal source to the SEL-300G through the ac protection cabinet wiring. (You may connect directly to the relay, however this does not verify the accuracy of the wiring in the protection cabinet.) Apply rated ac voltage (67 V1n, 120...
Vcb = +90° When setting PHROT = ACB, set angle Ia = 0° set angle Ib = 120° set angle Ic = -120° set angle Vab = -30° set angle Vcb = -90° SEL-300G Relay Quick-Start Installation Guide...
87 LED with input IN101. When rated dc voltage is applied to IN101, the 87 LED illuminates. Verify inputs IN201 through IN208 of SEL-300G_1 and SEL-300G_Y Relays using TAR 40. When input verification is complete, press the TARGET RESET or EXIT pushbutton to reset the front-panel target LEDs.
Relay Commissioning Procedure Table 3: SEL-300G Relay Contact I/O Viewed by the TAR Command LOP 60 TRIP 21/51V TAR 0 (Front-Panel LEDs) CLOSED TAR 1 27/59 (Front-Panel LEDs) TAR 31 OOST IN106 IN105 IN104 IN103 IN102 IN101 TAR 32 ALARM...
Page 21
3I0 meter value nearly zero. indicates a phase current polarity connection problem. If the relay is an SEL-300G1 or SEL-300G3 model, use the front-panel or serial port METER DIF command to check differential protection quantities. Differential operate current Note quantities IOP1, IOP2, and IOP3 should be near zero.
PRO R Statistic Buffers SER C Clears Sequential Events Record Buffer Set the Breaker Monitor function SEL control equation OGIC enable BKMON back to the setting specified by your Settings Sheets. If desired, use the SHO 1, SHO 2, SHO G, and SHO R commands to record the relay settings.
Reset generator operating profile PRO R =>> View/change passwords =>> Change settings =>> STA C Clear self-test status and restart relay =>> SYN R Clear synch-check reports and reset breaker close time average [300G2, 300G3] SEL-300G Relay Quick-Start Installation Guide...
Secondary Function DWG: Q300G002a Secondary) (see Figure 8) Figure 5: SEL-300G Front-Panel Pushbuttons – Overview Primary Functions Note in Figure 6 and Figure 7 that the front-panel pushbutton primary functions correspond to serial port commands – both retrieve the same information or perform the same function.
* Front-panel pushbutton functions that correspond to Access Level 1 serial port commands do not require the entry of the Access Level 1 password through the front panel. DWG: M300G137 Figure 6: SEL-300G Front-Panel Pushbuttons – Primary Functions Front-Panel Password Security Refer to the comments at the bottom of Figure 7 concerning Access Level B and Access Level 2 passwords.
Output contacts are pulsed for only 1 second from the front panel. Local control is not available through the serial port and does not require the entry of a password. DWG: M300G138a Figure 7: SEL-300G Front-Panel Pushbuttons – Primary Functions (continued) Secondary Functions...
*Front-panel pushbutton functions that correspond to Access Level 1 serial port commands do not require the entry of the Access Level 1 password through the front panel. DWG: M300G139a Figure 8: SEL-300G Front-Panel Pushbuttons – Secondary Functions SEL-300G Relay Quick-Start Installation Guide...
Step 4. Identify which drawout board needs to be changed. All SEL-300G models have a main board in the top guides, and Models 0300G_1 and 0300G_Y have an extra I/O board below the main board. Each board corresponds to a row of rear- panel screw-terminal blocks.
An extra alarm output contact can be obtained for all the SEL-300G models without the addition of any external hardware. The output contact next to the dedicated ALARM output contact can be converted to operate as an “extra alarm”...
Vdc is connected to Pin 1 on the corresponding EIA-232 serial ports. Table 11: EIA-232 Serial Port Voltage Jumper Positions for Standard Relay Shipments EIA-232 Serial Port 2 EIA-232 Serial Reference (rear panel) Port 3 (rear panel) Figures JMP2 = OFF JMP1 = OFF Figure 20 SEL-300G Relay Quick-Start Installation Guide...
Page 48
Against Test Bd; 16 hr @ +85°C Splashing IEC 60529:1989 [EN 60529:1992] IP54 Damp Heat, Water: from the front panel using the SEL-9103 Cyclic: IEC 60068-2-30:1980, Test Db; 25° to 55°C, 6 cycles, 95% humidity SEL-300G Relay Quick-Start Installation Guide...
20.0–200.0 V Pickup Time: 25 ms at 60 Hz (Max) Steady-State Voltage Definite-Time Accuracy: Pickup Range: ±5%, ±0.1 V 0.00–400.00 s Maximum Percentage Time-Delay Accuracy: ±0.1%, ±4.2 ms at 60 Hz (Max) Voltage Difference: 1.0–15.0% SEL-300G Relay Quick-Start Installation Guide...
Page 50
Timing: ±4%, ±25 ms at 60 Hz for |I| Angle: between 2 and 20 multiples of –20.0°–0.0° pickup Pickup Time: 50 ms at 60 Hz (Max) Zone 1 and Zone 2 Definite-Time Delays: 0.00–400.00 s SEL-300G Relay Quick-Start Installation Guide...
Page 51
0.1–50.0 ohms Equation Time-Delay Setting Range: Double Blinder: 0.00–3000.00 s Outer Resistance 0.2–100.0 ohms Desired time delay may be added using SEL Control OGIC Blinder: Equation Timers. Inner Resistance Blinder: 0.1–50.0 ohms 100 Percent Stator Ground Protection (64G): Steady-State Impedance...
Page 52
Supported, Field Selectable Time Delays: 0.03–400.00 s Trip, Alarm, and Ambient/Load-Current Bias Settings Maximum Definite-Time Up to 500 m fiber-optic cable to SEL-2600 Series RTD Delay Accuracy: ±0.1%, ±4.2 ms at 60 Hz Module Supervisory 27: 20–150 V, ±5%, ±0.1 V Measuring Range: –50°...
Page 53
±90° (power factor = 0) Metering accuracy calculation example for currents I and I due to preceding stated temperature coefficient: For temperature of 40°C, the additional error for currents , and I [(0.0002%)/(°C) ] * (40°C –20°C) = 0.08% SEL-300G Relay Quick-Start Installation Guide...
CT tap, per the CTR and CTRD settings. If mismatch remains on all three phases, check the CTR and CTRD settings to ensure that they are correct, per the actual CT ratio. SEL-300G Relay Quick-Start Installation Guide...
Then, I87 should lead IW1 by 150°. DWG: MAPP-E If E87 = T TRCON = GEN, CTCON = DAB TRCON = DACY, CTCON = Y TRCON = YDAB, CTCON = Y Then, I87 should lag IW1 by 150°. SEL-300G Relay Quick-Start Installation Guide...