2.3 Operation

2.3.1

Pre-operation checks

When installation and wiring are over, make the following checks prior to power-on.
1)
Check the wiring for incorrect connection. Especially check that the phase sequence and polarity of the main
circuit wiring are correct.
2)
Check for a short circuit caused by wire off-cuts.
3)
Check for loose terminal screws.
4)
Make sure that the machine is free of damage.
5)
Set the parameter values to match the operating machine system environment.
For the FR-A700, F700, A500, F500 or V500 series, set 2 (high power factor converter, power
regeneration common converter) in Pr. 30 "Regenerative function selection".
6)
Perform test operation after making sure that safety is ensured if the machine should become out of control.
7)
Perform test operation and make sure that the machine operates safely under light load at a low frequency.
After that, start operation.
Note: Do not conduct an insulation resistance test with a megger in the power regeneration common converter.
2.3.2

Power-on and operation

Before switching power on, check the following:
Installation check
Make sure that the inverter is installed correctly in a proper location. (Refer to page 10.)
• Wiring check
Make sure that the main and control circuits are wired correctly.
Make sure that the options and peripheral devices are selected and connected correctly.
(Refer to page 12.)
Switch power on.
Power-on is complete when the CHARGE lamp is lit correctly and the LED displays correct data.
The LED display gives the following indications at power-on.
LED
Display
Power on
During initialization
Converter
status
Note: If the cooling fan has stopped due to a fault, the LED display shows a flickering
(Refer to page 30.)
Start operation.
Turn on the start signal of the inverter. The motor accelerates to a given speed. At this time, the LED display of
the power regeneration common converter shows
Turn off the start signal of the inverter. The motor decelerates to a stop. The LED display of the power
regeneration common converter shows
LED
Display
Converter
status
Note: When the power regeneration common converter is regenerating power, the dedicated stand-alone reactor
generates sound but it is not a fault.
If the DC voltage is higher than
During alarm
the input power supply voltage
detection
at power-on, regenerative
operation is performed.
At this time, the bottom
segment flickers.
according to the magnitude of the regenerative energy.
Flicker
During driving operation
During regenerative operation
(During stop)
When the regeneration converter performs
switching operation, the bottom segment flickers.
Flicker
During normal

operation

(Driving status)
.
Flicker
23
Operation
. (400V class only)
2