Protecting The Digital Outputs From Flyback Voltages; Connecting To A Spring-Terminal Connector - National Instruments NI-9375 Getting Started

Hide thumbs Also See for NI-9375:
Table of Contents

Advertisement

Protecting the Digital Outputs from Flyback Voltages

If the channel is switching an inductive or energy-storing device such as a solenoid,
motor, or relay, and the device does not have flyback protection, install an external
flyback diode.
Figure 2. Connecting a Flyback Diode

Connecting to a Spring-Terminal Connector

What to Use
NI 9375 spring-terminal connector
2
0.08 mm
to 1.0 mm
(0.28 in.) of insulation stripped from the end
Flathead screwdriver with a 2.3 mm x 1.0 mm (0.09 in. x 0.04 in.) blade,
included with the NI 9375
What to Do
Complete the following steps to connect wires to the spring-terminal connector.
V
sup
DO
Flyback
Diode
DO COM
NI 9375
2
(28 AWG to 18 AWG) copper conductor wire with 7 mm
1
External
+
Power
Supply
Inductive
Device
2
3
NI-9375 Getting Started
© National Instruments
9

Advertisement

Table of Contents
loading