unit and the thermistor at the remote control unit. (The factory
shipment setting is at the indoor unit side.)
1. While operation is stopped, press and hold the TEST RUN button,
TEMP UP button and TEMP DOWN button simultaneously.
Press the FORWARD or BACK timer button to change the
temperature detection setting.
2. Press the SET button to complete the setting.
To change the setting, repeat the above operation.

24. GROUP CONTROL

Setting group for 1 remote control unit
- When using a remote control thermostat, the thermostat setting is
used for all indoor units in the group.
- During group control, up to a maximum of 16 indoor units can be
connected. (Do not mix heat pump units and cooling-only units.)
- Do not mix manual settings and automatic settings. (manual
settings take priority.)
- The master unit and slave units can be centralized controlled
during group control. /