Panasonic CS-A24BB4P Service Manual

Panasonic CS-A24BB4P Service Manual

Cassette type
Hide thumbs Also See for CS-A24BB4P:

Advertisement

CONTENTS

CASSETTE TYPE

Indoor Model / Outdoor Model
CS-A24BB4P / (CU-C24BBP5 / CU-A24BBP5)
CS-A28BB4P / (CU-C28BBP5 / CU-A28BBP5)
CS-A28BB4P / (CU-C28BBP8 / CU-A28BBP8)
CS-A28BB4P / (CU-C28BBP6)
CS-A34BB4P / (CU-C34BBP5 / CU-A34BBP5)
CS-A34BB4P / (CU-C34BBP8 / CU-A34BBP8)
CS-A34BB4P / (CU-C34BBP7)
CS-A43BB4P / (CU-C43BBP8 / CU-A43BBP8)
CS-A43BB4P / (CU-C43BBP7)
CS-A50BB4P / (CU-C50BBP8 / CU-A50BBP8)
CS-A50BB4P / (CU-C50BBP7)
Page
3
4
8
15
26
32
48
50
52
© 2001 Matsushita Air-Conditioning Corp. Sdn. Bhd.
(183914D). All rights reserved. Unauthorized copying
and distribution is a violation of law.
ORDER NO. MAC0112071C0

AIR CONDITIONER

(Cooling / Heat Pump)
Page
53
55
56
58
59
60
66
67

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CS-A24BB4P

  • Page 1: Table Of Contents

    ORDER NO. MAC0112071C0 AIR CONDITIONER CASSETTE TYPE Indoor Model / Outdoor Model (Cooling / Heat Pump) CS-A24BB4P / (CU-C24BBP5 / CU-A24BBP5) CS-A28BB4P / (CU-C28BBP5 / CU-A28BBP5) CS-A28BB4P / (CU-C28BBP8 / CU-A28BBP8) CS-A28BB4P / (CU-C28BBP6) CS-A34BB4P / (CU-C34BBP5 / CU-A34BBP5) CS-A34BB4P / (CU-C34BBP8 / CU-A34BBP8)
  • Page 2 CASSETTE TYPE 18 REACHING DISTANCE 27 CONTROL 19 SOUND DATA 28 WIRED REMOTE CONTROL INSTALLATION MANUAL 20 TWIN AND TRIPLE 29 WIRELESS REMOTE CONTROL INSTALLATION MANUAL 109 21 WIRING MISTAKE PREVENTION 30 INSTALLATION (INDOOR UNIT) 22 TEST OPERATION AND SELF DIAGNOSIS 31 INSTALLATION (OUTDOOR UNIT) 23 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH 32 REPLACEMENT PARTS...
  • Page 3: Service Information

    CASSETTE TYPE 1 SERVICE INFORMATION Notice of Address setting for NEW Cassette / NEW Outdoor Unit. The new Cassette / new Outdoor models are possible to have address setting for twin / triple control or group control automatically when main power supply is switched on. (Manual address setting is also possible by using DSW1 switch on the indoor unit P.C.
  • Page 4: Features

    CASSETTE TYPE 2 FEATURES Fan speed and suitable for offices, shops, homes etc, when 2.1. Variety of excellent features quiet operation is essential. • • Compact design • • Auto Swing Louvre Compact design 240 mm height, 840 mm width and 840 The air flow angle can be changed automatically (or mm depth.
  • Page 5: Product Features

    CASSETTE TYPE 2.2. Low-noise outdoor units 2.2.1. Product features 2.3. Greatly improved workability increases system renewal • • Low-noise design improves comfort in surrounding areas capability 1. The noise-suppre ssing winglet fan is a result of new research into vane design theory. The unique curved shape suppresses the generation of vortexes, thus reducing air flow noise.
  • Page 6 CASSETTE TYPE 2.4. A brand-new control method using the latest in technology • • Easier power supply wiring connection Power supply wiring and other wiring tasks can be carried out more easily. − − Twin non-polar wires used to connect indoor and outdoor units.
  • Page 7: Wired Remote Control

    CASSETTE TYPE 2.5. Wired Remote Control 2.6. Wireless Remote Control • • The new design includes an easily- visible red pilot lamp. The power can be turned on and off at a single touch, without opening the cover. • • Has a built-in thermistor, allowing indoor temperature detection in accordance with indoor conditions by switching •...
  • Page 8: Specification (Heat Pump Type )

    CASSETTE TYPE 3 SPECIFICATION (HEAT PUMP TYPE ) 3.1. CS-A24BB4P / CU-A24BBP5 ITEM / MODEL Indoor Unit Outdoor unit Main Body CS-A24BB4P CU-A24BBP5 Panel CZ-BT01P Remote CZ-RD51P (Wired) Control CZ-RL51P (Wireless) Cooling Capacity BTU/h 21,500 Heating Capacity BTU/h 24,200 Refrigerant Charge- less...
  • Page 9 2.61 2.61 Running Current Cool 12.3 12.0 11.7 Heat 12.0 11.7 11.4 Starting Current Power Factor Cool Heat *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220V, 230V, 240V 50Hz...
  • Page 10 2.61 2.61 Running Current Cool 4.50 4.45 4.40 Heat 4.30 4.25 4.20 Starting Current Power Factor Cool Heat *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 451V 50Hz...
  • Page 11 3.55 3.55 Running Current Cool 17.0 17.1 17.2 Heat 16.8 16.9 17.0 Starting Current Power Factor Cool Heat *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220V, 230V, 240V 50Hz...
  • Page 12 3.40 3.40 Running Current Cool 5.70 5.70 5.70 Heat 5.80 5.80 5.80 Starting Current Power Factor Cool Heat *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 415V 50Hz...
  • Page 13 Cool 4.25 4.25 4.25 Heat 4.10 4.10 4.10 Running Current Cool Heat Starting Current Power Factor Cool Heat *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 415V 50Hz...
  • Page 14 Cool 4.99 4.99 4.99 Heat 4.97 4.97 4.97 Running Current Cool Heat Starting Current Power Factor Cool Heat *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 415V 50Hz...
  • Page 15: Specification (Cooling Only Type )

    CASSETTE TYPE 4 SPECIFICATION (COOLING ONLY TYPE ) 4.1. CS-A24BB4P / CU-C24BBP5 ITEM / MODEL Indoor Unit Outdoor unit Main Body CS-A24BB4P CU-C24BBP5 Panel CZ-BT01P Remote CZ-RD51P (Wired) Control CZ-RL01P (Wireless) Cooling Capacity BTU/h 21,500 Refrigerant Charge- less Standard Air Volume for High,...
  • Page 16 Single Power Consumption Cool 2.69 2.69 2.69 Running Current Cool 12.3 12.0 11.7 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220V, 230V, 240V 50Hz...
  • Page 17 Condition by JIS B 8615 Volts Phase Single Power Consumption Cool 3.20 Running Current Cool 15.3 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220V, 60Hz...
  • Page 18 Phase Power Consumption Cool 2.69 2.69 2.69 Running Current Cool 4.50 4.45 4.40 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 415V 50Hz...
  • Page 19 Single Power Consumption Cool 3.60 3.60 3.60 Running Current Cool 17.00 17.10 17.20 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220V, 230V, 240V 50Hz...
  • Page 20 Condition by JIS B 8615 Volts Phase Power Consumption Cool 3.30 Running Current Cool 5.70 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3~220V, 60Hz...
  • Page 21 Phase Power Consumption Cool 3.30 3.30 3.30 Running Current Cool 5.70 5.70 5.70 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 415V 50Hz...
  • Page 22 Condition by JIS B 8615 Volts Phase Power Consumption Cool 5.10 Running Current Cool 15.0 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3~220V, 60Hz...
  • Page 23 Phase Power Consumption Cool 4.25 4.25 4.25 Running Current Cool 7.30 7.30 7.30 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 415V 50Hz...
  • Page 24 CS-A50BB4P, CU-C50BBP7 Condition by JIS B 8615 Volts Phase Power Consumption Cool Running Current Cool 17.7 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3~220V 60Hz...
  • Page 25 Phase Power Consumption Cool 4.99 4.99 4.99 Running Current Cool 8.60 8.60 8.60 Starting Current Power Factor Cool *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 415V 50Hz...
  • Page 26: Technical Drawing

    CASSETTE TYPE 5 TECHNICAL DRAWING...
  • Page 27 CASSETTE TYPE...
  • Page 28 CASSETTE TYPE...
  • Page 29 CASSETTE TYPE...
  • Page 30 CASSETTE TYPE...
  • Page 31 CASSETTE TYPE...
  • Page 32: Circuit Diagram

    CASSETTE TYPE 6 CIRCUIT DIAGRAM...
  • Page 33 CASSETTE TYPE...
  • Page 34 CASSETTE TYPE...
  • Page 35 CASSETTE TYPE...
  • Page 36 CASSETTE TYPE...
  • Page 37 CASSETTE TYPE...
  • Page 38 CASSETTE TYPE...
  • Page 39 CASSETTE TYPE...
  • Page 40 CASSETTE TYPE...
  • Page 41 CASSETTE TYPE...
  • Page 42 CASSETTE TYPE...
  • Page 43 CASSETTE TYPE...
  • Page 44 CASSETTE TYPE...
  • Page 45 CASSETTE TYPE...
  • Page 46 CASSETTE TYPE...
  • Page 47 CASSETTE TYPE...
  • Page 48: Operating Instruction

    CASSETTE TYPE 7 OPERATING INSTRUCTION 7.1. Wired Remote Control (OPTIONAL PARTS) NOTES: • • Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct. • • The illustration above is for explanatory purposes only. The appearance will be different during actual operation. •...
  • Page 49 CASSETTE TYPE 7.2. Wireless Remote Control (OPTIONAL PARTS) NOTES: • • Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct. • • The illustration above is for explanatory purpose only. The appearance will be different during actual operation. •...
  • Page 50: Refrigeration Cycle

    CASSETTE TYPE 8 REFRIGERATION CYCLE CS-A24BB4P/CU-A24BBP5, CS-A28BB4P/CU-A28BBP5, CS-A28BB4P/CU-A28BBP8, CS-A34BB4P/CU-A34BBP5, CS-A34BB4P/CU-A34BBP8, CS-A43BB4P/CU-A43BBP8, CS-A50BB4P/CU-A50BBP8...
  • Page 51 CASSETTE TYPE CS-A24BB4P/CU-C24BBP5, CS-A28BB4P/CU-C28BBP5, CS-A28BB4P/CU-C28BBP6, CS-A28BB4P/CU-C28BBP8, CS-A34BB4P/CU-C34BBP5, CS-A34BB4P/CU-C34BBP7, CS-A34BB4P/CU-C34BBP8, CS-A43BB4P/CU-C43BBP7, CS-A43BB4P/CU-C43BBP8, CS-A50BB4P/CU-C50BBP7, CS-A50BB4P/CU-C50BBP8...
  • Page 52: Operation Range

    CASSETTE TYPE 9 OPERATION RANGE Power Supply The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage.
  • Page 53: Pipe Length

    CASSETTE TYPE 10 PIPE LENGTH n n CORRECTION OF COOLING CAPACITY AND HEATING CAPACITIES Correction of cooling and heating capacities according to the connecting pipe length. The data of cooling capacities (marked on the name plate) are based on 5 meters connecting pipe and horizontal installation. For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity.
  • Page 54 CASSETTE TYPE n n REFRIGERANT ADDITIONAL CHARGE n Heat pump type 1. Piping installation by standard piping • • At the time of shipment from the factory, this unit is Model Name Standard piping specification charged with enough refrigerant for an equivalent pipe Liquid Gas piping Gas charge-...
  • Page 55: Operating Characteristic

    Compressor Motor Indoor Unit Fan Outdoor unit Fan Motor Motor Voltage Frequency S.C. R.C. (A) IPT (kW) R.C. R.C. (Hz) Cool/Heat Cool/Heat (kW) (kW) CS-A24BB4P 10.6 2.31 0.40 0.08 0.50 0.11 CU-C24BBP5 10.2 2.31 0.40 0.08 0.50 0.11 2.31 0.40 0.08 0.50...
  • Page 56: Fan Performance

    CASSETTE TYPE 12 FAN PERFORMANCE CS-A24BB4P ITEM / MODEL Indoor Unit Outdoor Unit CS-A24BB4P CU-A24BBP5, CU-C24BBP5 MODE Air Volume /min Running Current 0.38 0.31 0.27 0.50 Power 0.08 0.07 0.06 0.11 Consumption Fan Speed r/min CS-A34BB4P ITEM / MODEL Indoor Unit...
  • Page 57 CASSETTE TYPE CS-A43BB4P CS-A50BB4P ITEM / MODEL Indoor Unit Outdoor Unit ITEM / MODEL Indoor Unit Outdoor Unit CS-A43B4P CU-A43BBP5, CS-A50B4P CU-A50BBP8, CU-C43BBP7, CU-C50BBP7, CU-C34BBP8 CU-C50BBP8 MODE MODE Air Volume /min Air Volume /min Running Current 0.90 0.80 0.70 1.10 Running Current 0.90 0.80...
  • Page 58: Safety Device

    CASSETTE TYPE 13 SAFETY DEVICE INDOOR UNIT Heat pump model Indoor unit CS-A24BB4P CS-A28BB4P CS-A34BB4P CS-A43BB4P CS-A50BB4P Cooling only model For Fan Motor Protection, °C Internal Protector (49F) °C For Control Protection, Fuse 3.15 3.15 3.15 3.15 3.15 OUTDOOR UNIT...
  • Page 59: Component Specification

    Direct on-line Starting Type Rated Output Poles Insulation Class Type MS32 MS32 Sontex200LT Sontex200LT Sontex200LT Sontex200LT Charge Evaporator Models CS-A24BB4P CS-A28BB4P CS-A34BB4P CS-A43BB4P CS-A50BB4P Tube Material Copper tube Outer Diameter Thickness 0.27 0.27 0.27 0.27 0.27 No. of Tubes/Row Fin Material...
  • Page 60: Capacity And Power Consumption

    15 CAPACITY AND POWER CONSUMPTION 15.1. HEATING PERFORMANCE Model Heating capacities are based on conditions below. Model Heating capacities are based on conditions below. CS-A24BB4P 1 phase, 50Hz, 230V CS-A28BB4P 1 phase, 50Hz, 230V Heating capacity Indoor temperature 20°C D.B.
  • Page 61 CASSETTE TYPE Model Heating capacities are based on conditions below. Model Heating capacities are based on conditions below. CS-A34BB4P 1 phase, 50Hz, 230V CS-A34BB4P 3 phase, 50Hz, 400V Heating capacity Indoor temperature 20°C D.B. Heating capacity Indoor temperature 20°C D.B. 11.2 kW Outdoor temperature 7°C D.B.
  • Page 62 CASSETTE TYPE Model Heating capacities are based on conditions below. Model Heating capacities are based on conditions below. CS-A43BB4P 3 phase, 50Hz, 400V CS-A50BB4P 3 phase, 50Hz, 400V Heating capacity Indoor temperature 20°C D.B. Heating capacity Indoor temperature 20°C D.B. 14.0 kW Outdoor temperature 7°C D.B.
  • Page 63: Cooling Performance

    CASSETTE TYPE 15.2. COOLING PERFORMANCE Model Cooling capacities are based on conditions below. Model Cooling capacities are based on conditions below. CS-A24BB4P 1 phase, 50Hz, 230V CS-A28BB4P 1 phase, 50Hz, 230V Cooling capacity Indoor temperature 27°C D.B. 19°C W.B. Cooling capacity Indoor temperature 27°C D.B.
  • Page 64 CASSETTE TYPE Model Cooling capacities are based on conditions below. Model Cooling capacities are based on conditions below. CS-A34BB4P 1 phase, 50Hz, 230V CS-A34BB4P 3 phase, 50Hz, 400V Cooling capacity Indoor temperature 27°C D.B. 19°C W.B. Cooling capacity Indoor temperature 27°C D.B. 19°C W.B. 10.0 kW Outdoor temperature 35°C D.B.
  • Page 65 CASSETTE TYPE Model Cooling capacities are based on conditions below. Model Cooling capacities are based on conditions below. CS-A43BB4P 3 phase, 50Hz, 400V CS-A50BB4P 3 phase, 50Hz, 400V Cooling capacity Indoor temperature 27°C D.B. 19°C W.B. Cooling capacity Indoor temperature 27°C D.B. 19°C W.B. 12.5 kW Outdoor temperature 35°C D.B.
  • Page 66: Discharge And Suction Pressure

    CASSETTE TYPE 16 DISCHARGE AND SUCTION PRESSURE...
  • Page 67: Position Of The Center Gravity

    CASSETTE TYPE 17 POSITION OF THE CENTER GRAVITY MODEL NAME OUTSIDE DIMENSIONS NET WEIGHT CENTRE OF GRAVITY WIDTH (mm) DEPTH (mm) HEIGHT (mm) X (mm) Y (mm) Z (mm) CU-A24BBP5 CU-C24BBP5 CU-A28BBP5 CU-A28BBP8 CU-C28BBP5 CU-C28BBP6 CU-C28BBP8 CU-A34BBP5 1220 CU-A34BBP8 1220 CU-C34BBP5 1220 CU-C34BBP7...
  • Page 68: Reaching Distance

    CASSETTE TYPE 18 REACHING DISTANCE...
  • Page 69 CASSETTE TYPE...
  • Page 70: Sound Data

    CASSETTE TYPE 19 SOUND DATA...
  • Page 71 CASSETTE TYPE...
  • Page 72 CASSETTE TYPE...
  • Page 73 CASSETTE TYPE...
  • Page 74 CASSETTE TYPE...
  • Page 75: Twin And Triple

    CASSETTE TYPE 20 TWIN AND TRIPLE • • Master unit and slave- units can be set automatically in twin 20.1. Twin and Triple Operation and triple systems. No address setting is necessary. • • Simultaneous air conditioning of wide spaces and corners is •...
  • Page 76 CASSETTE TYPE Turn on the power supply. 20.1.2. Automatic address setting for twin Operation: The unit will operate as slave unit 1. and triple systems Automatic address setting is not carried out at this time. Procedure: Turn on the power supply for the indoor and outdoor units.
  • Page 77: Piping Connections

    CASSETTE TYPE • • The indoor units will not run for approximatel y 1 minute • • Do not turn off the power supply for at least 1 minute after while automatic twin/triple address resetting is being carried automatic twin/triple address resetting has been carried out. out.
  • Page 78: Refrigerant Charging

    CASSETTE TYPE 20.3. Refrigerant charging • • For twin and triple-type systems The pipe length is the total of the branch pipe (L) and the junction pipes (la → lb → lc in order from the thickest diameter). At the point where the pipe length exceeds 30 m, determine the amount of refrigerant for the remaining liquid-side pipe diameters and pipe lengths from the following table in order to charge the system.
  • Page 79 CASSETTE TYPE 20.4. Wiring...
  • Page 80: Wiring Mistake Prevention

    CASSETTE TYPE 21 WIRING MISTAKE PREVENTION Improved quality of installation work through adoption of an “Connection error prevention” circuit which prevents wiring mistakes Connection errors with the control wires and the power supply wires will not only contribute to burning-out of the control circuit board, but can also cause large-scale working losses and affect reliability.
  • Page 81: Test Operation And Self Diagnosis

    CASSETTE TYPE 22 TEST OPERATION AND SELF DIAGNOSIS 22.1. Test operation 22.3. Test operation using the wired • • Always use a properly-insu lated tool to operate the switch remote control on the circuit board. (Do not use your finger or any metallic object).
  • Page 82 CASSETTE TYPE 22.4. Test operation using the wireless remote control <Air conditioner No.> − − The air conditioner No. “01” appears during normal installation and use. When using group control, a different number may appear. The air conditioner No. can be displayed by pressing the air conditioner No. button.
  • Page 83 CASSETTE TYPE How to display the past error message An error code from 1F15 to 1F49 will be displayed. (The temperature setting display will also change to show the If the “CHECK” display on the wired remote control is not air conditioner No.) flashing, press the CHECK button continuously for 5 seconds or more to display the problem details for the last problem or...
  • Page 84 CASSETTE TYPE...
  • Page 85: Setting Of Save Energy And Thermistor Switch

    CASSETTE TYPE 23 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH 23.1. Energy save setting 23.2. Switching to the remote • • Upper and lower limit can be set for the setting temperature control thermistor during cooling and heating operation. (The factory shipment •...
  • Page 86: Group Control

    CASSETTE TYPE 24 GROUP CONTROL Setting group for 1 remote control unit be determined automatically after approximatel y 1 minute. • • When using a remote control thermostat, the thermostat (DIP switch settings are not necessary.) setting is used for all indoor units in the group. NOTE: •...
  • Page 87: Troubleshooting

    CASSETTE TYPE 25 TROUBLESHOOTING If test operation does not proceed correctly section C) Symptom: Carry out test operation after approximately 12 hours have passed Remote control unit... Display of “No power supply” since the power was turned on (crankcase heater is energized). If operation is started by using the remote control within 1 minute of NOTE: turning on the power, the outdoor unit settings will not be made...
  • Page 88 CASSETTE TYPE 1. The main power is turned on while the transmission connection cord is not connected (open circuit at section wires between the indoor unit(s) are not connected (open circuit at section A) Symptom: Symptom: − − Remote control unit.. . Display of “No power supply” Nothing abnormal appears on the remote control −...
  • Page 89 CASSETTE TYPE 1. The main power is turned on while the transmission unit No. 2 is possible. wires between the indoor unit and the outdoor unit are However, indoor unit No. 3 cannot be operated. not connected (open circuit at section A) Symptom: Operation of indoor unit No.
  • Page 90 CASSETTE TYPE 1. Automatic address setting (don’t need to set dip-switch) Reset the address by following the procedure: If the wiring is connected properly as above example, the a. After making sure that dip-switches No. 1 to 4 and No. address is set automatically by the main power supply.
  • Page 91 CASSETTE TYPE Procedures of deleting memory for twin/triple control system 1. Switch off the main power supply. 2. Set the No. 8 pin of dip switch (DSW1) at the indoor unit’s P.C. board to “ON” position. 3. Switch on the main power supply for a minute and then turn it off.
  • Page 92: Emergency Operation

    CASSETTE TYPE 26 EMERGENCY OPERATION Emergency operation Thermistor Cooling mode Heating mode • • Emergency operation of outdoor unit Indoor unit Room temperature Fixed at 25°C Pipe temperature Shorted Open Emergency operation can be carried out by setting the DSW1 switch on the printed circuit board of the outdoor Thermistor Cooling mode Heating mode unit to the EMERGENCY position.
  • Page 93: Control

    CASSETTE TYPE 27 CONTROL Description of basic Functions 27.1. Cooling mode operation time chart (*1) Outdoor unit fan start control during cooling At the start of cooling mode and drying mode operation, the outdoor unit heat exchanger outlet temperature is detected in order to set the fan speed.
  • Page 94: Drain Pump Control

    CASSETTE TYPE • • Remote control displays and indoor unit operation continue during this time. • • The 10 minutes countdown is cleared if the compressor stops or if the temperature at the outdoor unit outlet rises to 13.5°C or higher.
  • Page 95 CASSETTE TYPE (When float switch is continuously off) <If the float switch operates again after turning off> <If the float switch continues to be off> 27.3. Freezing prevention control 1. Operation During cooling mode operation, after 9 minutes have passed since the compressor turned on, the outdoor unit will stop its operation when the temperature detected by the indoor unit pipe temperature sensor is 2°C or lower.
  • Page 96 CASSETTE TYPE 27.4. Heating mode operation time chart (Heat pump type) (*2) Outdoor unit fan control during heating mode operation When the compressor is on during heating mode operation (except during defrosting and when the liquid bypass valve is on), the outdoor unit fan is controlled by means of input (CN2) indicating whether the contact of the heating pressure switch on the outdoor unit circuit board is open or closed.
  • Page 97 CASSETTE TYPE 27.5. Hot starting 1. When heating mode operation starts a. Start Hot start control commences when heating mode operation starts. b. Operation “PREHEAT” appears on the remote control display. (Other displays remain unchanged.) The indoor unit fan stops. In addition, during hot starting, the louvre stays at the horizontal position (angle 0°). c.
  • Page 98 CASSETTE TYPE 2. When defrosting is completed a. Start Hot start control commences when defrosting is completed. b. Operation “PREHEAT” appears on the remote control display. (Other displays remain unchanged) The indoor unit fan stops. In addition, during hot starting, the louvre stays at the horizontal position (angle 0°C). c.
  • Page 99 CASSETTE TYPE 27.7. Excess heat dissipation for indoor unit The indoor unit fan continue its operation for 30 seconds after heating mode operation turns off in order to dissipate excess heat. 1. When heating mode operation has stopped (LOW speed for 30 seconds) 2.
  • Page 100 CASSETTE TYPE c. Forced defrosting If P8 on the outdoor unit circuit board is shorted while the compressor is on during heating mode operation and the temperature detected by the outdoor unit heat exchanger outlet sensor is 25°C or lower, defrosting is carried out regardless of the current starting conditions.
  • Page 101 CASSETTE TYPE 3. Thermostat characteristic s during automatic changeover operation a. Settings at the start of automatic changeover operation When operation changes from other modes to automatic changeover mode, operation starts at the temperature characteristic s given in the table below. b.
  • Page 102: Indoor Unit Fan Control

    CASSETTE TYPE 27.10. Indoor unit fan control 1. Fixing at LO, MED or HI When LO, MED or HI is set, the relay switches and operation is carried out at that setting. 2. Automatic fan speed When set to AUTO, the indoor unit fan operation changes as shown in the table below. (Indoor temperature) - (Setting temperature) (Units: K) Mode / Fan Speed Cooling...
  • Page 103: Discharge Temperature Control

    CASSETTE TYPE 2. During initial operation When the OFF/ON button is pressed to start the operation, the louvre moves through one full cycle, and then swings automatically (if AUTO has been set using the remote control) or moves to the setting angle (if MANUAL has been set using the remote control).
  • Page 104: Wired Remote Control Installation Manual

    CASSETTE TYPE 28 WIRED REMOTE CONTROL INSTALLATION MANUAL...
  • Page 105 CASSETTE TYPE...
  • Page 106 CASSETTE TYPE...
  • Page 107 CASSETTE TYPE...
  • Page 108 CASSETTE TYPE...
  • Page 109: Wireless Remote Control Installation Manual

    CASSETTE TYPE 29 WIRELESS REMOTE CONTROL INSTALLATION MANUAL...
  • Page 110 CASSETTE TYPE...
  • Page 111 CASSETTE TYPE...
  • Page 112 CASSETTE TYPE...
  • Page 113 CASSETTE TYPE...
  • Page 114 CASSETTE TYPE...
  • Page 115 CASSETTE TYPE...
  • Page 116: Installation (Indoor Unit)

    CASSETTE TYPE 30 INSTALLATION (INDOOR UNIT)
  • Page 117 CASSETTE TYPE...
  • Page 118 CASSETTE TYPE...
  • Page 119 CASSETTE TYPE...
  • Page 120 CASSETTE TYPE...
  • Page 121 CASSETTE TYPE...
  • Page 122 CASSETTE TYPE...
  • Page 123 CASSETTE TYPE...
  • Page 124 CASSETTE TYPE...
  • Page 125: Installation (Outdoor Unit)

    CASSETTE TYPE 31 INSTALLATION (OUTDOOR UNIT)
  • Page 126 CASSETTE TYPE...
  • Page 127 CASSETTE TYPE...
  • Page 128 CASSETTE TYPE...
  • Page 129 CASSETTE TYPE...
  • Page 130 CASSETTE TYPE...
  • Page 131 CASSETTE TYPE...
  • Page 132 CASSETTE TYPE...
  • Page 133 CASSETTE TYPE...
  • Page 134: Replacement Parts

    CASSETTE TYPE 32 REPLACEMENT PARTS 32.1. INDOOR UNIT...
  • Page 135 CASSETTE TYPE...
  • Page 136 CASSETTE TYPE PART DESCRIPTION QTY. CS-A24BB4P CS-A28BB4P CS-A34BB4P CS-A43BB4P CS-A50BB4P ← ← ← ← ← ← ← ← BASE PAN ASS’Y CWD52K1034 ← ← ← ← ← ← INNER POLYSTYRENE (TOP) CWG071049 CWG071057 ← ← ← ← ← ← INNER POLYSTYRENE (SIDE)
  • Page 137 CASSETTE TYPE...
  • Page 138 CASSETTE TYPE PART DESCRIPTION PART NO. QTY. FRONT GRILLE CWE121026 COVER-AIR SWING MOTOR CWH811013 CONNECTOR- SHAFT CWH081002 CONNECTOR- SHAFT CWH081003 CONNECTOR- SHAFT CWH081004 BEARING CWH641006 VANE CWE241103 CONNECTOR- SHAFT CWH081005 CONNECTOR- SHAFT CWH081006 AIR SWING MOTOR CWA981065 INSULATION POLYSTYRENE CWG071105 INSULATION POLYSTYRENE CWG071106 INSULATION POLYSTYRENE...
  • Page 139 CASSETTE TYPE 32.2. OUTDOOR UNIT...
  • Page 140 CASSETTE TYPE...
  • Page 141 CASSETTE TYPE...
  • Page 142 CASSETTE TYPE...
  • Page 143 CASSETTE TYPE PART DESCRIPTION QTY. CU-A24BBP5 CU-A28BBP5 CU-A28BBP8 ← ← ← ← BASE PAN ASS’Y CWD52K1038A COMPRESSOR NH41VNDT NH44VNDT NH44YDET ← ← ← ← ANTI-VIBRATION BUSHING CWH501018 ← ← ← ← NUT FOR COMP. MOUNT. XNG8 ← ← ← ← WASHER for COMPRESSOR XWA8 ←...
  • Page 144 CASSETTE TYPE PART DESCRIPTION QTY. CU-C24BBP5 CU-C28BBP5 CU-C28BBP6 CU-C28BBP8 ← ← ← ← ← ← BASE PAN ASS’Y CWD52K1038A COMPRESSOR NH41VNDT NH44VNDT NH44NADT NH44YDET ← ← ← ← ← ← ANTI-VIBRATION BUSHING CWH501018 ← ← ← ← ← ← NUT FOR COMP. MOUNT. XNG8 ←...
  • Page 145 CASSETTE TYPE...
  • Page 146 CASSETTE TYPE...
  • Page 147 CASSETTE TYPE...
  • Page 148 CASSETTE TYPE...
  • Page 149 CASSETTE TYPE PART DESCRIPTION QTY. CU-A34BBP5 CU-A34BBP8 CU-A43BBP8 CU-A50BBP8 ← ← ← ← BASE PAN ASS’Y CWD52K1039A CWD52K1040A COMPRESSOR ZR47K3PFJ522 ZR45KCTFD522 ZR57KCTFD599 ZR68KCTFD599 ← ← ← ← ← ← ANTI-VIBRATION BUSHING CWH501020 ← ← ← ← ← ← NUT FOR COMP. MOUNT. 4582065 ←...
  • Page 150 CASSETTE TYPE PART DESCRIPTION QTY. CU-C34BBP5 CU-C34BBP7 CU-C34BBP8 CU-C43BBP7 CU-C43BBP8 CU-C50BBP7 CU-C50BBP8 ← ← ← ← ← ← ← ← ← ← BASE PAN ASS’Y CWD52K1039A CWD52K1040A COMPRESSOR ZR47K3PFJ522 ZR45KCTF5522 ZR45KCTFD522 ZR57KCTF5599 ZR57KCTFD599 ZR68KCTF5599 ZR68KCTFD599 ← ← ← ← ← ← ←...
  • Page 151: Heating Capacity Performance Data

    H.C. = Heating Capacity IPT = Power Consumption Model Heating capacities are based on conditions below. Model Heating capacities are based on conditions below. CS-A24BB4P 1 phase, 50Hz, 230V CS-A28BB4P 1 phase, 50Hz, 230V Heating capacity Indoor temp. 20°C D.B.
  • Page 152: Cooling Capacity Performance Data

    CASSETTE TYPE 34 COOLING CAPACITY PERFORMANCE DATA Model Power Source Entering Temperature Air Entering Condeser (°C D.B.) (CS-) 25 °C 30 °C 35 °C 40 °C 43 °C Temperature SHC IPT D.B. W.B. A24BB4P 230V, 6.30 4.13 1.95 5.99 4.04 2.13 5.67 3.94...
  • Page 153 SHC = Sensible Heat Capacity IPT = Power Consumption Model Cooling capacities are based on conditions below. Model Cooling capacities are based on conditions below. CS-A24BB4P 1 phase, 50Hz, 230V CS-A28BB4P 1 phase, 50Hz, 230V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B.

Table of Contents