TC = Total Cooling Capacity
IPT = Power Consumption
Model
Cooling capacities are based on
conditions below.
CS-
A43BB4P
3 phase, 50Hz, 400V / Indoor
Cooling
temperature 27°C D.B. 19°C W.B. /
capacity
Outdoor temperature 35°C D.B. /
12.5 kW
Standard air volume 30m
Entering
Air
25
Temperature
TC
D.B.
W.B.
kW
17
12.7
27
19
13.8
22
15.0
Entering
Air
25
Temperature
IPT
D.B.
W.B.
kW
17
3.39
27
19
3.63
22
3.88
/min
3
Temperature Air Entering
Condenser (°C D.B.)
30
35
40
TC
TC
TC
kW
kW
kW
12.1
11.5
10.9
13.1
12.5
11.8
14.3
13.7
13.2
Temperature Air Entering
Condenser (°C D.B.)
30
35
40
IPT
IPT
IPT
kW
kW
kW
3.71
4.04
4.39
3.91
4.25
4.62
4.18
4.55
4.80
43
TC
kW
10.2
11.0
12.2
43
IPT
kW
4.70
4.90
5.04