27.10. Indoor unit fan control
1. Fixing at LO, MED or HI / When LO, MED or HI is set, the relay
switches and operation is carried out at that setting.
2. Automatic fan speed / When set to AUTO, the indoor unit fan
operation changes as shown in the table below.
Mode / Fan Speed
Cooling
Heating
Fan
27.11. Forced operation during restart
The compressor will not stop operating for 3 minutes after cooling mode operation starts, even
if the indoor unit thermostat turns off. / (However, the compressor will stop operating during
this time if the indoor unit air intake temperature drops to 16°C and below during cooling mode
operation.)
27.12. Louvre control (models with louvre)
1. When main power is turned on / When the power is turned on,
indoor unit louvre position detection is carried out twice and then
the indoor unit louvre stops.
(Indoor temperature) - (Setting temperature) (Units
HI
+3 or higher
-3 or lower
MED irrespective of temperature
146
MED
+1.5 ~ 3
-1.6 ~ - 3
LO
Less than +1.5
More than -1.5