WARNING for Using R32/R290 Refrigerant
• When flammable refrigerant are employed, appliance
shall be stored in a well -ventilated area where the room
size corresponds to the room area as specifiec for opera-
tion.
For R32 frigerant models:
Appliance shall be installed, operated and stored in a
room with a floor area larger than 4m2 . For R290 refrig-
erant models, appliance shall be installed, operated and
stored in a room with a floor area larger than:
<=9000Btu/h units: 13m2
> 9000Btu/h and <=12000Btu/h units: 17m2
> 12000Btu/h and <=18000Btu/h units: 26m2
> 18000Btu/h and <=24000Btu/h units: 35m2
• Reusable mechanical connectors and flared joints are not
allowed indoors. (EN Standard Requirements).
• Mechanical connectors used indoors shall have a rate of
not more than 3g/year at 25% of the maximum allow-
able pressure. When mechanical connectors are reused
indoors, sealing parts shall be renewed. When flared
joints are reused indoors, the flare part shall be re-fabri-
cated. (UL Standard Requirements)
• When mechanical connectors are reused indoors, sealing
parts shall be renewed. When flared joints are reused
indoors, the flare part shall be re-fabricated. (IEC Standard
Requirements)
• Mechanical connectors used indoors shall comply with ISO
14903.
European Disposal Guidelines
This marking shown on the product or its literature, indicates that waste electrical and
eletrical equipment should not be mixed with genera/ household waste.
4
102
man_S60xx EU ('21) V3.indd 102
man_S60xx EU ('21) V3.indd 102
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
09-11-2021 09:05
09-11-2021 09:05

Advertisement

Table of Contents
loading

This manual is also suitable for:

S6026

Table of Contents