4.2.36 Output (remote input) function selection (Pr. 190 to Pr. 192)

Pr. 190 " ( RX2 ) function selection"
Pr. 191 " ( RX6 ) function selection"
Pr. 192 "A, B, C terminal ( RX7 ) function selection"
You can change the functions of the contact output terminals (remote input).
Parameter
(Remote Input)
Number
190
191
192
<Setting>
Refer to the following table and set the parameters:
Signal
Setting
Name
0
RUN
1
SU
3
OL
4
FU
11
RY
12
Y12
13
Y13
98
LF
99
ABC
Note: 1. The same function may be set to more than one terminal (remote input).
2. Pr. 190 to Pr. 192 do not function if the values set are other than the above.
Terminal
Factory
Setting
Symbol
(RX2)
(RX6)
ABC(RX7)
Function
Inverter running
Up to frequency
Overload alarm
Output frequency
detection
Inverter operation
ready
Output current
detection
Zero current
detection
Minor fault output
Alarm output
Factory-Set Terminal
Function
0
Inverter running
4
Frequency detection
99
Alarm output
Operation
Output during operation when
the inverter output frequency
rises to or above the starting
frequency.
Refer to Pr. 41 "up-to-frequency
sensitivity". (Note 1)
Output while stall prevention
function is activated.
Refer to Pr. 42, Pr. 43 (output
frequency detection).
Output when the inverter is
ready to be started by switching
the start signal on.
Refer to Pr. 150 and Pr. 151
(output current detection).
Refer to Pr. 152 and Pr. 153
(zero current detection).
Output when a minor fault
occurs.
Output when the inverter's
protective function is activated to
stop the output (major fault).
132
PARAMETERS
Setting
Range
0 to 99
0 to 99
0 to 99
Related
Parameters

Pr. 41
Pr. 22, Pr. 23,
Pr. 66
Pr. 42, Pr. 43

Pr. 150,
Pr. 151
Pr. 152,
Pr. 153
Pr. 244
