(5) Recommendation of bar terminals
For wiring of the CC-Link communication signals, two CC-Link dedicated cables must
be twisted together and connected to one terminal block.
When using bar terminals, the following terminals and tool are recommended.
1) Recommended bar terminal, crimping tool
! Company: Phoenix Contact Co., Ltd.
! Bar terminal type: AI-TWIN2×0.5-8WH
! Crimping tool type: CRIMPFOX UD6, ZA3
2) Connection of terminal resistor
Connect a terminal resistor between terminals DA-DB of the inverter located at the
end.
Work the resistor attached to the master unit of the PLC for use as the terminal
resistor.
Note: When there is no resistor attached to the
master unit, use a commercially available
110Ω, 1/2W resistor.
3) Connection of shield wire of the CC-Link dedicated cable
Twist the shield wire of the CC-Link dedicated cable and connect it to terminal SLD.
Note: The two SLD terminals are connected in the inverter.
Tube
Cut the tube.
Cut.
INSTALLATION AND WIRING
Shield wire
24