Mitsubishi FR-E520-0.1KN Instruction Manual page 96

Table of Contents

Advertisement

<Setting>
! Use Pr. 21 to set the acceleration/deceleration time and minimum setting
increments:
Set value "0" (factory setting) ....... 0 to 3600 seconds
Set value "1" ................................. 0 to 360 seconds
! Use Pr. 7 and Pr. 44 to set the acceleration time required to reach the frequency
set in Pr. 20 from 0Hz.
! Use Pr. 8 and Pr. 45 to set the deceleration time required to reach 0Hz from the
frequency set in Pr. 20.
! Pr. 44 and Pr. 45 are valid when the RT signal is on.
! Set "9999" in Pr. 45 to make the deceleration time equal to the acceleration time
(Pr. 44).
Note: 1. In S-shaped acceleration/deceleration pattern A (refer to page 88), the set
time is the period required to reach the base frequency set in Pr. 3.
• Acceleration/deceleration time calculation expression when the set
frequency is the base frequency or higher
4
9 ×
t =
• Guideline for acceleration/deceleration time at the base frequency of 60Hz
(0Hz to set frequency)
Frequency setting (Hz)
Acceleration/
deceleration time (s)
2. When the setting of Pr. 7, Pr. 8, Pr. 44 or Pr. 45 is "0", the acceleration/
deceleration time is 0.04 seconds. At this time, set 120Hz or less in Pr. 20.
3. When the RT signal is on, the other second functions such as second torque
boost are also selected.
4. If the shortest acceleration/deceleration time is set, the actual motor
acceleration/deceleration time cannot be made shorter than the shortest
acceleration/deceleration time determined by the mechanical system's GD
and motor torque.
(minimum setting increments: 0.1 second)
(minimum setting increments: 0.01 second)
T
5
× f
2
+
9 T
2
(Pr. 3)
T: Acceleration/deceleration time setting(s)
f : Set frequency (Hz)
5
15
60
120
5
12
15
35
81
PARAMETERS
200
400
27
102
82
305
4
2

Advertisement

Table of Contents
loading

Table of Contents