Leakage Current; Power Limitations; Cabinet Stability; Accessories - HP Rack System/E User Manual

Rack system/e
Table of Contents

Advertisement

Chapter 1

Leakage Current

WARNING
Due to types of products that can be installed in this cabinet, there is a risk of
high leakage current (3.5 mA). Reliable ground circuit continuity is vital for
safe operation of this product. To reduce the risk of electric shock, earth
(ground) connection is essential before connecting the power supply. Never
operate this cabinet with the ground conductor disconnected.

Power Limitations

CAUTION
To reduce the risk of overload, do not load any single PDU with more than a
maximum of 16 Amperes. In addition, do not load a single NEMA 5-15 or
IEC-320 receptacle with more than 15 Amperes.

Cabinet Stability

CAUTION
To reduce the risk of cabinet instability, fully extend the anti-tip mechanism
before extending any devices. Extend only one device at a time. Do not
stand or sit on any extended device. Qualified service personnel should do
all non-operator servicing.

Accessories

CAUTION
This product is designed for use with specific electrical accessories (i.e.,
PDUs and fans). The use of any other accessory is not recommended or
supported.