General; Concise Product Description; Setting Table - Nibe FIGHTER 1240 Installation And Maintenance Instructions Manual

230 v uk
Table of Contents

Advertisement

2
In order to get the ultimate benefit from your heat pump FIGHTER 1240 you should read through
this Installation and Maintenance Instruction.
FIGHTER 1240 is a heat pump central for the production of heating and domestic hot water in
detached and terrace houses. Soil, rock or lakes can be used as the heat source.
FIGHTER 1240 is a Swedish made quality product offering a long life span and safe operation.
For the installation engineer: Please, hand over to the home owner his manual after finalised
installation.
The serial number (95)
spondence with NIBE.
_ _ _ _ _ _ _ _ _ _ _ _ _ _
FIGHTER 1240- _ _
Installation date
Anti-corrosion
Enamel
Installation engineers
The type of brine – Mixing proportion/freezing point
Active drilling depth/collector length
Commissioning checks
Brine temperature (in/out) ____ / ____
(Nominal temperature diff 2 - 5 °C)
Temperature heat medium (supply/return)____ / ____
(Nominal temperature diff 5 - 10 °C)
Settings
Menu
1.4 Start time.HW ............. 47
1.5 Stop temp.HW .............. 54
1.6 Stop Temp. XHW ............. 60
1.8 Interval XHW
.............. 14
2.1 Curve coefficient ...........
2.2 Offset heating curve .....
2.3 Flow temp./MIN .............. 15
2.4 Flow temp./MAX .............. 55
2.7 Return temp./MAX ......... 53
Date ________
Signed ____________________________
Completed by the installer when the heat pump is installed
,
should always be stated with all corre-
Stainless steel
Pump setting
Factory
Position
settings
100 Fuse
101 Max electr. output ......
102 Max boiler temp .......
9
5

General

Manufacter:
NIBE AB
Box 14
Järnvägsgatan 40
285 21 MARKARYD
SWEDEN
Maximum water
supply pressure
Copper
Immersion heater
Operating pressure, tap water
Expansion vessel, tap water,
charge pressure
Expansion vessel, heating water,
charge pressure
Pressure reduction valve, setting
Volume, water heater
Mass, unit, filled with water
___
___
Maximum primary working
Pump setting
pressure (heating side)
Set opening pressure of
Factory
temperature and pressure valve
settings
Set opening pressure relief valve
........
20
Set opening, temperature limiter,
C
immersion heater
C (65)
Set opening, temperature limiter,
compressor
Heating up time from
15 °C to 65 °C
Re-heating time to 65 °C 5 kW 1 h 47 min
70 % of total volume
FIGHTER 1240
16 bar
R50 / 6000 W / 230 V
6 bar
3,5 bar
0,5 bar
3,5 bar
160 litres
5 kW
485 kg
8 kW
505 kg
12 kW 515 kg
2,5 bar
7 bar
6 bar
88 °C
88 °C
5 kW
3 h 0 min
8 kW 2 h 40 min
12 kW 2 h 15 min
8 kW 1 h 41 min
12 kW 1 h 38 min