In order to get the ultimate benefit from your heat pump FIGHTER 1140 you should read through this Installation and Maintenance Instruction. FIGHTER 1140 is a base heat pump for heating small houses, apartment blocks and industrial premises. Soil, rock or lakes can be used as the heat source.
System description Principle of operation FIGHTER 1140 consists of a heat pump, circulation Ground water can also be used as a heat source. This pumps and a control system for the heat pump and requires an intermediate heat exchanger. additional heat.
(the accessory ESV 21 is required). Heating system symbols Shown when house heating is in progress. Second row: Value of the current parameter. Third row: Description of current display para- meter. “Hot water temp” is normal- ly shown. FIGHTER 1140...
Page 7
Summer mode: changes. Only production of hot water using FIGHTER 1140. The circulation pump and immersion heater are blocked. However, when “Extra hot water” is activated Right keypad the immersion heater is connected. Plus button...
2.1 by one increment. Warm weather conditions If the room temperature is low, increase the “Heat- ing curve offset” setting by one step. If the room temperature is high, reduce the “Heating curve offset” setting by one step. FIGHTER 1140...
Settings Setting using diagrams Heating curve offset -2 The heating control system on the FIGHTER 1140 is HEATING CURVE VÄRMEKURVA controlled by the outside temperature. This means the °C flow temperature is regulated in relation to the current 15 14 13 12 outdoor temperature.
The setting is made on menu 9.2.12 “Brinepump 10 days”. Fixed condensing If required FIGHTER 1140 can be docked to an exter- nal unit with its own heating controls. FIGHTER 1140 then delivers heat up to a fixed temperature level. This is known as “fixed condensing”.
Max length per collector should not exceed 400 m. Where there is more than one collector, they must be FIGHTER 1140 is placed on a firm base, preferably a connected in parallel, with a means of adjusting the concrete floor or foundation. FIGHTER 1140 should flow.
50 °C and an outgoing max tempera- ture from the heat pump of approximately 60 °C. Ventilation recovery Since FIGHTER 1140 is not fitted with shut-off valves, these must be fitted outside of the heat pump to facili- The installation can be supplemented with the exhaust air module FLM to provide ventilation recovery.
Electrical connection Connection FIGHTER 1140 must not be connected without the permission of the electricity supplier and must be con- Cable glands for Cable glands for nected under the supervision of a qualified electrician. sensors the supply FIGHTER 1140 must be installed via an isolator switch with a minimum breaking gap of 3 mm.
-X9 to 230 V + PE via the junction box with fuses. Connection on delivery 230 V -8, -12 230 V: The heat pump is connected on terminal block -X9 to 230 V + PE via the junction box with fuses. FIGHTER 1140...
The heat pump is connected on terminal block -X9 to 3 x 400 V + N + PE via the junction box with fuses. Phase sequence monitor FIGHTER 1140- 15, 17 3x400V ■ Orange LED is lit at correct phase sequence.
Connection on delivery 3 x 230 V (only applies to Norway) 3 x 230 V: The heat pump is connected on terminal block -X9 to 3 x 230 V + PE via the junction box with fuses. FIGHTER 1140...
VPA. porarily or periodically raise or lower the flow tempera- ture and with that the room temperature. Connected to terminals X1:3 and X1:4 on the EBV-card (2). See Menu 2.5 for settings. Hot water, jacket External compensation 1 FIGHTER 1140...
X1:5 and X1:7. Tariff B, the compressor is disconnected. Connect a potential free contact function to terminals X1:6 and X1:7. Tariff A and Tariff B can be combined. A made contact results in the electrical output being disconnected. FIGHTER 1140...
Electrical connection External contacts RG 10, sensor for changing the room temp. An external sensor can be connected to FIGHTER 1140 to change the flow temperature and with that set the room temperature, for example, a room sensor (RG 10, accessory).
Alarm output, common alarm Soft-start relay* FIGHTER 1140 is equipped with a soft-start relay (97), which limits the inrush current, see section “Technical specifications”. The compressor must not be forced to start with peri- ods shorter that 1 start per 15 minutes.
SÄV Safety valve Boiler temperature sensor Included with FIGHTER 1140 Flow sensor Included with FIGHTER 1140 Hot water temperature sensor (88) Included with FIGHTER 1140 Outdoor temperature sensor Included with FIGHTER 1140 Return temperature sensor Included with FIGHTER 1140 VVB/ACK Accumulator with water heater e.g.
Page 26
Docking Option 1 - FIGHTER 1140 docked with immersion heater and hot water heater (floating condensing) SÄV SÄV ELVVB VVB / ACK BK / JK Menu option Principle of operation This option requires the following selections to be FIGHTER 1140 prioritises hot water charging via a made in: shuttle valve (VXV).
Docking Option 1 - FIGHTER 1140 docked with immersion heater and hot water heater (floating condensing) Connection of the outside temperature Connection of hot water sensor sensor Outside temperature sensor (UG) Hot water, jacket (VVG) Connection VST 11* -M19 Shuttle valve X1 -X6 * Accessories.
Docking Option 2 - FIGHTER 1140 docked to a gas boiler (floating condensing) Gas boiler Gaspanna SÄV SÄV SÄV SÄV SF AV VVB / ACK BK / JK Principle of operation Menu option FIGHTER 1140 prioritises charging the hot water This option requires the following selections to be heater (VVB/ACK).
Page 29
Docking Option 2 - FIGHTER 1140 docked to a gas boiler (floating condensing) Sensor connection Immersion heater connection for XHW Flow line sensor 1 (FG) Return sensor 1 (RG) Hot water, jacket (VVG) Immersion heater for XXV Elpatron för XVV...
Docking Option 3 - FIGHTER 1140 docked to an oil-fired boiler (floating condensing) Oljepanna Oil boiler SÄV SÄV SF AV VVB / ACK BK / JK Principle of operation Menu option FIGHTER 1140 prioritises charging the hot water This option requires the following selections to be heater (VVB/ACK).
Page 31
Docking Option 3 - FIGHTER 1140 docked to an oil-fired boiler (floating condensing) Connection of shunt valve* Sensor connection -X6:20 closes the shunt valve. -X6:21 opens the shunt valve. -X6:22 zero conductor. Flow line sensor 1 (FG) Return sensor 1 (RG)
Docking Option 4 - FIGHTER 1140 docked to another heat source (fixed condensing) Accessory or Tillbehör alt befintlig regler- existing control utrustning. equipment SÄV SÄV VVB / ACK Wood-fired boiler BK / JK Vedpanna Principle of operation Menu option FIGHTER 1140 charges the hot water heater/accumu- This option requires the following selections to be lator tank (VVB/ACK).
Page 33
Docking Option 4 - FIGHTER 1140 docked to another heat source (fixed condensing) Connection of the outside temperature Connection of the flow sensor sensor Outside temperature sensor (UG) Flow line sensor 1 (FG) Return sensor 1 (RG) Hot water, jacket (VVG)
17. Fill the level vessel with liquid up to around 2/3. 18. Open the valve below the level vessel. Internal air vent valve, brine 19. Select “Off” in menu 9.2.4. 20. Select the auto operating mode using the operating mode button. FIGHTER 1140...
11. Adjust the heating curve offset knob so there is a heating requirement. The compressor will start. 12. If the heat pump is a FIGHTER 1140-12, 15, 17, check the direction of rotation at start-up of the compressor.
Rotation check Fighter 1140-15, 17 kW 3x400 V Fighter 1140-12 kW 3x400 V The compressor in FIGHTER 1140-12 kW 3 x400 V is The compressor in FIGHTER 1140-15, 17 kW of the scroll type. It can only operate in one direction 3 x400 V is of the scroll type.
After filling, open the valve again. To raise the pressure, close the valve on the incoming main pipe when the brine pump (KBP) is running and the level vessel (NK) is open, so that water is drawn in from the vessel. FIGHTER 1140...
The key sym- bol will then be shown on the display. The 2. Enter button same procedure is used to deactivate the key lock. NOTE! Ensure the operating mode is not changed during quick movement FIGHTER 1140...
Return to 8.0 ■ Press the minus button to move to menu 8.5 ■ Press the enter button to move to menu 8.0 ■ Press the plus button to move to menu 1.0 Normal menus Expanded menus Service menus FIGHTER 1140...
↵ ↵ Offset cold curve Return to 2.0 2.9.3 Starttemp. cooling 2.9.4 Diff Passive/Active 2.9.5 Cooling 2.9.5 ↵ ↵ Return to 2.9.0 * Only shown when “On” is selected in menu 9.2.13.3. Normal menus Expanded menus Service menus FIGHTER 1140...
Page 41
↵ ↵ Return to 5.0 * Only shown when “On” is selected in menu 9.2.5. for shunt group 2 (accessory ESV 21 required). ** Shown when the accessory RG 10 is installed. Normal menus Expanded menus Service menus FIGHTER 1140...
Page 42
8.4.1 8.4.0 ↵ ↵ Pooltemp./Setting Pool adjustments ↵ ↵ Return to 7.0 8.4.2 Diff. Pool ↵ ↵ Return to 8.0 8.4.3 Pool Time 8.4.4 Pool heating 8.4.5 ↵ ↵ Return to 8.4.0 Normal menus Expanded menus Service menus FIGHTER 1140...
Page 43
Boiler temp/act mixv 9.2.17 TB-alarm activated 9.2.13.5 Start value OilPower 9.2.18 Roomsensor type 9.2.13.6 Oil burner on 9.2.19 Type of HW sensor 9.2.13.7 ↵ ↵ Return to 9.2.13.0 9.2.20 ↵ ↵ Return to 9.2.0 Normal menus Expanded menus Service menus FIGHTER 1140...
Extended, shows all menus except the Readings regarding the temperatures and compressor service menus. are made from the sub-menus to this menu. Service, shows all menus, returns to the previous menu level 30 minutes after the * Accessories last button was pressed. FIGHTER 1140...
S e t t e m p e r a t u r e curve slope or heating curve offset. 2 . 6 . 3 Menu 2.6.3 Set temperature Here you select at what outside temperature the break point shall occur. The value is adjustable between -15 and +15 °C. FIGHTER 1140...
Page 47
Menu 2.10 Return Pressing the enter button returns you to menu 2.0. Menu 2.9.1 Cooling curve The selected cooling curve (curve slope) is shown here. The value can be set between curve 1 and 3. *only applies with HPAC accessory FIGHTER 1140...
3 . 6 . 3 curve slope or heating curve offset. Menu 3.6.3 Set temperature 2 Here you select at what outside temperature the break point shall occur. The value is adjustable between -15 and +15 °C. FIGHTER 1140...
R e t u r n ational. 4 . 2 “Compr. ON” means that the compressor is opera- tional. Menu 4.2 Return “Brine pump on” means the brine pump is running. Pressing the enter button returns you to menu 4.0. FIGHTER 1140...
R e t u r n Menu 5.22 Max temp cond. flow 6 . 4 This menu shows the max permitted temperature for Menu 6.4 Return condenser flow line. Pressing the enter button returns you to menu 6.0. FIGHTER 1140...
7 . 4 . 1 0 Menu 7.3.3 - 7.3.9 Set Time Monday - Sunday Menu 7.4.10 Return The time for the day change, e.g. night reduction is Pressing the enter button returns you to menu 7.4.0 chosen here. FIGHTER 1140...
0 and 2. Idle mode occurs 30 minutes after the last button was pressed. R e t u r n 0=shut-off, 1=low, 2=average. 7 . 8 Menu 7.8 Return Pressing the enter button returns you to menu 7.0. FIGHTER 1140...
Page 53
M a x e l e c . s t e p Pressing the enter button returns you to menu 8.2.0 8 . 3 . 5 Menu 8.3.5 Max elec. step The setting selected on the EBV card (2) knob (101) is shown here. FIGHTER 1140...
Menu 9.1.1 Start BIN 3 step Degree-minute deficiency before additional heat is engaged. When the power step has reduced the degree-minutes deficiency by 100 in relation to the set start value it is disengaged. The value is adjustable between -30 and -500. FIGHTER 1140...
S y s t e m 2 P r e s e n t 9 . 2 . 5 Menu 9.2.5 System 2 Present This menu is used to select “On” or “Off” depending on whether you have shunt group 2 (accessory ESV 21 needed). FIGHTER 1140...
Page 56
The flow temperature is increased from 20 to 45 °C for 4 days, it then remains constant for 3 days. The temperature then steps down to 25 °C for 4 days, and then returns to the normal settings. FIGHTER 1140...
Page 57
Menu 9.2.14 Factory setting Linear 3 step: Selected with an external electric boiler. Return to the factory settings in FIGHTER 1140, “Yes” Binary 7 step: Selected with an external electric boiler. or “No”. When returning to the factory settings the lan- guage switches to English.
Pressing the enter button returns you to menu 9.4.0. R e t u r n 9 . 2 . 2 0 Menu 9.2.20 Return Pressing the enter button returns you to menu 9.2.0 FIGHTER 1140...
Menu 9.5.4 Brine In Menu 9.5.5 Brine Out Menu 9.5.6 Outdoor temp. Menu 9.5.7 Flow temp. Menu 9.5.8 Return temp. Menu 9.5.9 Hot water temp. Menu 9.5.10 Hot gas temp. Menu 9.5.11 Compr. time Menu 9.5.12 Electric b. time FIGHTER 1140...
The following alarms block hot water charging to draw This information is shown when the high pressure attention to the alarm. The operating mode switches to switch in FIGHTER 1140 has tripped. The compressor winter mode and additional heat engages. is blocked and FIGHTER 1140 switches to winter...
Page 61
This information is shown when a fault on the hot water temperature sensor has been registered. FIGHTER 1140 is force-run solely for hot water charging and automatic mode is engaged. The alarm B O I L E R S E N S O R may be due to: 1 .
Page 62
This information is displayed when the flow tempera- ture between the condensor and immersion heater reaches 65 °C or more. If the operating disturbance cannot be rectified by means of the above, an installation engineer should be called. FIGHTER 1140...
NOTE! High room temperature Cause: Incorrect setting of “Curve slope” and/or As FIGHTER 1140 can be connected “Heating curve offset”. to a large number of external units Action: Adjust the setting. even these should be checked.
It is usually easier to start the circulation pump with FIGHTER 1140 running, switch (8) set to “1”. If help- ing the circulation pump to start is performed with FIGHTER 1140 running, be prepared for the screw- driver to jerk when the pump starts.
Service connection, low pressure 165*** Terminal block X221, compressorheater Expansion valve Accessories ** Enclosed *** 10, 12, 15, 17 kW 3x400 V The component list refers to all the different types of heat pump. See each component position picture. FIGHTER 1140...
4 x (ø28 x R25 int.) Part no 024 035 Tubes for Outside temperature F1140 10-15 (kW) sensors sensor 2 x (ø28 x R25 int.) Part no 024 035 Part no 408 017 Part no 018 764 2 x (ø35 x R32 int.) Part no 424 283 FIGHTER 1140...
Part no 089 304 Level monitor NV 10 Passive cooling module Part no 089 315 PKM 10 (intended for 5 - 8 kW) Part no 089 397 PKM 20 (intended for 10 - 17 kW) Part no 089 398 FIGHTER 1140...
665 020 665 021 * Compressor output only. ** Regards brine in temperature / heat medium flow temperature in accordance with EN 255. *** The compressor produces up to 65 °C, the rest is obtained using additional heating. FIGHTER 1140...
Enclosure class IP 21 Weight (kg) Part No 665 010 665 011 665 012 665 013 665 014 665 015 * Compressor output only. ** Regards brine in temperature / heat medium flow temperature in accordance with EN 255. FIGHTER 1140...
Regards brine in temperature / heat medium flow temperature in accordance with EN 255. Regards brine in temperature / heat medium flow temperature in accordance with EN 14511. The compressor produces up to 65 °C, the rest is obtained using additional heating. FIGHTER 1140...
Need help?
Do you have a question about the FIGHTER 1140 and is the answer not in the manual?
Questions and answers