Step 12 Connecting The Power And Communication Cables - Samsung AM TN4 KH Series Installation Manual

Table of Contents

Advertisement

CAUTION
• When the float switch is not detected due to
insufficient water on the drain pan, the drain
pump will not work.
• If the power supply is directly connected to the L
and N terminals, communication error message
might appear.
• After completing the drainage check, turn the unit
off and disconnect the power supply.
• Reassemble the control box cover.
c Check whether the drain pump works correctly.
d Check whether the drainage is performing
correctly at the end of the drain pipe.
e Check for leakage at the drain pipe and drain pipe
connection part.
f When leakage occurs, check whether the indoor
unit is level and check the drain hose connection
part, drainpipe connection part and drain pump
connection.
g When the drainage check is completed and
the condensed water remains on the drain pan,
remove the water.
Step 12 Connecting the power and
communication cables
Power and communication cable connection
• Before wiring work, you must turn off all power source.
• Connect the power and communication cable among
the units within maximum length to set the voltage
drop under 10%.
• The auxiliary circuit breaker (ELCB, MCCB, ELB) should
be considered more capacity if many indoor units are
connected from one breaker.
• Connect F3, F4(for communication) to the
communication cable of the wired remote control.
• Tighten the electric wires with a proper tool within the
torque limit to connect and fix them firmly, and then
organize the wires to prevent outside pressure being
exerted on the covers and other parts. Failure to do so
may result in overheating, electric shock, and fire.
Tightening torque (N•m)
M3.5
M4
(1 N•m = 10 kgf•cm)
• To protect the product from water and possible shock,
you should keep the power and the communication
cables of the indoor and outdoor units in the iron pipe.
• Connect the power cable to the auxiliary circuit
breaker (ELCB, MCCB, ELB).
• Keep distances of 50mm or more between power cable
and communication cables.
• Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
H07RN-F)
• Screws on terminal block must not be unscrewed with
the torque less than 12 kgf•cm.
• When installing the indoor unit in a computer room,
use the double shielded (tape aluminum / polyester
braid + copper) cable of FROHH2R type.
0.8 ~ 1.2
1.2 ~ 1.8
15