Mitsubishi Electric PUHZ-FRP71VHA2 Service Manual page 61

Hide thumbs Also See for PUHZ-FRP71VHA2:
Table of Contents

Advertisement

SW2 setting
FTC pipe temperature/liquid (TH2)
ON
−39–88
1
2 3 4 5 6
Outdoor pressure sensor satu-
ON
rated temperature (63HS)
−39–88
1
2 3 4 5 6
Discharge superheat SHd
0–186
ON
TH4 − 63HS
1
2 3 4 5 6
Sub cool
0–130
ON
Cooling: 63HS–TH3
Heating: 63HS–TH2
1
2 3 4 5 6
DHW, Cooling & DHW: 63HS–TH34
Heating & DHW: "63HS–TH2" or
"63HS–TH34", whichever is lower.
Compressor operating frequency
0–255
ON
1
2 3 4 5 6
LEV-A opening pulse
0–480
ON
1
2 3 4 5 6
LEV-B opening pulse
0–480
ON
1
2 3 4 5 6
LEV-C opening pulse
0–480
ON
1
2 3 4 5 6
Compressor operating current
0–50
ON
1
2 3 4 5 6
OCH665B
Display detail
−39–88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39–88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
0–186
(When the temperature is 100°C or more, hundreds digit,
tens digit and ones digit are displayed by turns.)
0–130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
0– 255
(When it is 100Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 125Hz;
0–480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 150 pulse;
0–480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0–480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0–50
Note: Omit the figures after the decimal fractions.
The black square ( ) indicates a switch position.
Explanation for display
0.5 s
0.5 s
1
0.5 s
0.5 s
61
0.5 s
2 s
1
25
0.5 s
2 s
50
0.5 s
2 s
1
30
0.5 s
2 s
1
30
Unit
°C
°C
°C
°C
Hz
Pulse
Pulse
Pulse
A