Type of
Switch No.
Switch
1
2
SW5
3,4
5
Forced refrigerant recovery
1
2
SW7
3
5
6
1
SW8
2
Dip
3
Separate power supply
switch
1
Cooling & DHW simultaneous operation
SW9
2
3,4
SW5
6
1
2
3
4
SW6
5
6
7
8
SW7
4
*2
'Power failure automatic recovery' can be set by either remote controller or this DIP SW. If one of them is set to ON, 'Auto
recovery' activates. Please set "Auto recovery" basically by remote controller because all units do not have DIP SW.
Please refer to the indoor unit installation manual.
SW7-1 is setting change over of Demand/Low noise. It is effective only in the case of external input.
*3
(Local wiring is necessary. Refer to next page: Special function)
OCH665B
Function
No function
Power failure
*2
automatic recovery
No function
*3
Mode select
No function
No function
Operation priority
Defrost setting
Cooling operation limit
Fan table select
No function
No function
Model select
The black square ( ) indicates a switch position.
Action by the switch operation
ON
—
Auto recovery
No auto recovery
—
Start
Demand function
Low noise mode
—
—
ATW
For high humidity
None
2nd table
Separate
Comfort
—
—
55
Effective timing
OFF
—
When power supply ON
—
When compressor is
Normal
working in ATA cooling, ATA
heating and ATW heating.
Always
—
—
ATA
When power supply ON
Normal
Always
16 hr
Always
1st table
Always
Normal
When power supply ON
Eco
Always
—
—
—
—
—
—
—
—