Phenomena
6. Remote controller display works
normally and the unit performs cool-
ing operation, however, the capacity
cannot be fully obtained. (The air
does not cool well.)
7. Remote controller display works
normally and the unit performs
heating operation, however, the
capacity cannot be fully obtained.
8. For 3 minutes after temperature
adjuster turns off, the compressor
will not start operating even if tem-
perature adjuster is turned on.
For 3 minutes after temperature
adjuster turns on, the compressor
will not stop operating even if tem-
perature adjuster is turned off.
(Compressor stops operating imme-
diately when turning off by the
remote controller.)
OCH665B
Factor
1 Refrigerant shortage
2 Filter clogging
3 Heat exchanger clogging
4 Air duct short cycle
1 Linear expansion valve fault
Opening cannot be adjusted well due to linear
expansion valve fault.
2 Refrigerant shortage
3 Lack of insulation for refrigerant piping
4 Filter clogging
5 Heat exchanger clogging
6 Air duct short cycle
7 Bypass circuit of outdoor unit fault
12 Normal operation
(For protection of compressor)
1 • If refrigerant leaks, discharging tempera-
ture rises and LEV opening increases.
Inspect leakage by checking the tem-
perature and opening.
• Check pipe connections for gas leak-
age.
2 Open intake grille and check the filter.
Clean the filter by removing dirt or dust
on it.
3 • If the filter is clogged, indoor pipe tem-
perature rises and discharging pressure
increases. Check if heat exchanger is
clogged by inspecting discharging pres-
sure.
• Clean the heat exchanger.
4 Remove the blockage.
1 • Discharging temperature and indoor heat
exchanger temperature does not rise.
Inspect the failure by checking
discharging pressure.
• Replace linear expansion valve.
2 • If refrigerant leaks, discharging
temperature rises and LEV opening
increases.
Inspect leakage by checking the
temperature and opening.
• Check pipe connections for gas leakage.
3 Check the insulation.
4 Open intake grille and check the filter.
Clean the filter by removing dirt or dust
on it.
5 • If the filter is clogged, indoor pipe
temperature rises and discharging
pressure increases. Check if heat
exchanger is clogged by inspecting
discharging pressure.
• Clean the heat exchanger.
6 Remove the blockage.
7 Check refrigerant system during
operation.
12 Normal operation
36
Countermeasure