Mitsubishi Electric PUHZ-FRP71VHA2 Service Manual page 5

Hide thumbs Also See for PUHZ-FRP71VHA2:
Table of Contents

Advertisement

2-3. PRECAUTIONS WHEN REUSING EXISTING R22 REFRIGERANT PIPES
(1) Flowchart
• Refer to the flowchart below to determine if the existing pipes can be used and if it is necessary to use a filter dryer.
• If the diameter of the existing pipes is different from the specified diameter, refer to technical data materials to confirm if the
pipes can be used.
The existing pipe thickness meets specifica-
tions and the pipes are not damaged.
Check if the existing air conditioner can operate.
After operating the cooling system for about 30
minutes, do a pump down work.
Disconnect the existing air conditioner from the
pipes.
Attach the new air conditioner
Perform the airtight test, vacuum air purging,
additional refrigerant charging (if necessary),
and gas leak check.
Test run
OCH665B
Measure the existing pipe thickness and
check for damage.
• If the existing air conditioner cannot operate, use a
refrigerant recovery device to collect the refrigerant.
• If the existing pipes have been used for gas or oil
heat pump system, use new pipes.
5
The existing pipe thickness does not meet
specifications or the pipes are damaged.
The existing pipes cannot be reused.
Use new pipes.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Puhz-frp71vha2r1

Table of Contents