PARAMETERS LIST

Below the list of the parameters used to program the Master unit. The parameters are divided into 7 main
groups used to identify the specific field function of every parameter.
6.1

PARAMETERS GROUPS

Parameters CF

Parameters ST
Parameters EX
Parameters BK
Parameters RO
Parameters OL
Parameters RT
6.1.1
PARAMETERS CF
This group contain all those parameters used to configure the master unit and to setup the whole system.
These specific parameters can be changed only when the system is in OFF mode.
Parameter
Description
System regulation selection:
CF01
0=proportional
1=neutral zone
System working mode;
0=only cooling
CF02
1=only heating
2=heating and cooling
Cooling regulation probe definition:
0= evaporator inlet temperature (connected to Master or Slave
controllers)
CF03
1= evaporator outlet temperature (connected to Master or
Slave controllers)
2= tank temperature (connected to the Master controller)
Heating regulation probe definition
0= evaporator inlet temperature (connected to Master or Slave
controllers)
1= evaporator outlet temperature (connected to Master or
Slave controllers)
CF04
2= condenser inlet temperature (connected to Master or Slave
controllers)
3= condenser outlet temperature (connected to Master or
Slave controllers)
4= tank temperature (connected to the Master controller)
CF05
Number of slave units present in the system
CF06
Modbus address of the unit considered as the first one
Engineering unit selection:
CF07
0=°C (with decimal resolution)
1=°F (with integer resolution)
CF08
Weight defined for the 1
CF09
Weight defined for the 2
CF10
Weight defined for the 3
CF11
Weight defined for the 4
CF12
Weight defined for the 5
CF13
Weight defined for the 6
CF14
Weight defined for the 7
CF15
Weight defined for the 8
CF16
Weight defined for the 9
CF17
Weight defined for the 10
Input selection of the changeover
0=none
CF18
1=digital input
2=keyboard
CF19
Regulation delay at power on
CF20
Password setting for level 2 access
CF21
Password setting for level 3 access
User manual IPM500 EN rel1.0.doc
Configuration parameters group
Thermoregulation parameters group
Expansion board parameters group
Back-up unit parameters group
Units rotation parameters group
Overboost & Limiter parameters group
Timebands parameters group
SYSTEM CONFIGURATION PARAMETERS
SLAVE UNITS WEIGHTS CONFIGURATION PARAMETERS
st
slave
nd
slave
rd
slave
th
slave
th
slave
th
slave
th
slave
th
slave
th
slave
th
slave
COMMON UTILITIES CONFIGURATION PARAMETERS
PASSWORDS CONFIGURATION PARAMETERS
Minimum
Maximum
Value
Value
0
1
0
2
0
2
0
4
2
10
1
247
0
1
0.0
100.0
0.0
100.0
0.0
100.0
0.0
100.0
0.0
100.0
0.0
100.0
0.0
100.0
0.0
100.0
0.0
100.0
0.0
100.0
0
2
0
999
0
9999
0
9999
iPro Series
UM
Resolution
-
-
-
-
-
-
-
-
-
-
-
-
-
-
%
Dec
%
Dec
%
Dec
%
Dec
%
Dec
%
Dec
%
Dec
%
Dec
%
Dec
%
Dec
-
-
sec
-
-
-
-
-
26/48