Download Print this page

Technical Data - S+S Regeltechnik THERMASGARD TM54 Series Operating Instructions, Mounting & Installation

Immersion ⁄ screw-in ⁄ duct temperature measuring transducer, calibratable, with multi-range switching and active output

Advertisement

Available languages

Available languages

  • ENGLISH, page 6
G
THERMASGARD
®
Calibratable temperature measuring transducer THERMASGARD
measuring ranges and continuous output, with connecting head made from aluminium (optionally
with cable gland or M12 connector according to DIN EN 61076-2-101) and straight protective tube.
A basic unit in four variants through combination with accessories, eg, for robust applications with
a separate immersion sleeve made from stainless steel. The duct sensor is used to detect tempera-
tures in liquid or gaseous media. It is used in pipes, heating engineering, storage systems, compact
district heating stations, warm and cold water systems, oil and lubrication cycle systems, mechanical,
apparatus and plant engineering and throughout the industrial sector.
calibrated; an environmental precision adjustment by an expert is possible.

TECHNICAL DATA

Power supply:
Working resistance:
Load resistance:
Power consumption:
Sensor:
Measuring ranges:
Deviation, temperature:
Output:
Connection type:
Electrical connection:
Cable connection:
Dimensions:
Connecting head:
Protective tube:
Process connection:
Humidity:
Protection class:
Protection type:
Standards:
ACCESSORIES
TH-ms  ⁄ xx
TH-VA  ⁄ xx
TH-VA  ⁄ xx  ⁄ 90
MF-06-M
Type ⁄ WG01
TM 54 - I PT1000 xx (EL) MM
TM 54 - U PT1000 xx (EL) MM
TM 54 - I PT1000 xx KV (EL) MM
TM 54 - U PT1000 xx KV (EL) MM
TM 54 - I PT1000 xx Q (EL) MM
TM 54 - U PT1000 xx Q (EL) MM
Installation length: ( E L )M M = 50 mm, 100 mm, 150 mm, 200 mm, 250 mm, 300 mm, 350 mm, 400 mm
Optional versions see catalog or webshop.
TM 54
24 V AC ⁄ DC (± 10 %) for U variant
15...36 V DC for I variant, depending on working resistance,
residual ripple stabilised ± 0.3 V
R
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant
a
b
R
> 5 kOhm for U variant
L
< 1.0 VA ⁄ 24 V AC ⁄ DC; < 0.55 VA ⁄ 24 V DC
Pt1000, DIN EN 60571, class B
(Perfect Sensor Protection)
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
T
= +150°C
max
with manual zero point correction (± 10 K)
typically ± 0.2 K at +25 °C
0 - 10 V or 4...20 mA
2- or 3-wire connection
2
0.2 - 1.5 mm
, via push-in terminal
TM 54 (standard)
adjusting screw made of metal (M 20 x 1.5)
TM 54-KV (optional)
cable gland, brass, nickel-plated
(M 20 x 1.5 ; with strain relief, exchangeable,
inner diameter 6 - 12 mm)
TM 54-Q (optional)
M12 connector according to DIN EN 61076-2-101
(male, 5-pin, A-code)
see dimensional drawing
form B, material aluminium,
colour white aluminium (similar to RAL 9006),
ambient temperature –30...+70 °C
stainless steel, V4A (1.4571) Ø = 6 mm,
inserted length (EL) = 50 - 400 mm (see table)
by means of immersion sleeve or mounting flange (accessories)
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 54 (according to EN 60 529) TM 54
IP 65 (according to EN 60 529) TM 54-KV / TM 54-Q
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
Immersion sleeve, brass, nickel-plated,
Ø = 8 mm, T
= +150 °C, p
max
max
Immersion sleeve, stainless steel, V4A (1.4571),
Ø = 8 mm, T
= +600 °C, p
max
max
Immersion sleeve, stainless steel, V4A (1.4571),
with neck tube (90 mm), Ø = 8 mm, T
Mounting flange, metal, galvanised steel, Ø = 32 mm,
Ø = 6.3 mm tube gland, T
max
Sensor
Pt1000
Pt1000
Pt1000
Pt1000
Pt1000
Pt1000
®
TM 54 with eight switchable
The sensor is factory-
= 10 bar
= 40 bar
= +600 °C, p
= 40 bar
max
max
= +700 °C
Rev. 2022 - V23
Connectinga diagram
-
-
230V AC
+
+
24V DC
1 2 3 4
+ –
Pt1000
DIP offset
ON
1 2 3
Connectinga diagram
-
-
230V AC
+
+
24V DC
1 2 3 4 5
Pt1000
DIP
offset
ON
1 2 3
Output
4...20 mA
0 - 10 V
4...20 mA
0 - 10 V
4...20 mA
0 - 10 V
TM 54 - I
Bürde
TM 54 - U
SPS
PC

Advertisement

loading

This manual is also suitable for:

Tm54 seriesTm 54-kvTm 54-q