Commissioning Of An External Battery Cabinet - Chloride VA 1000 User Instruction Manual

Active and e-series uninterruptible power supply
Table of Contents

Advertisement

4.1 Commissioning of an External Battery Cabinet

The following table shows the designations of the battery cabinets which are available for the UPS devices.
Table 2. External Battery Packs
Model
Active 700
NA
Active 1000
BPActive1000-19
Active 2000
BPActive3000-19
Active 3000
BPActive3000-19
Disconnect the UPS from the mains and the loads from the UPS.
CAUTION: Make sure that the circuit breaker on the external battery cabinet is in the OFF position.
CAUTION: Battery cabinets are not interchangeable. Use ONLY the battery cabinet indicated above.
Connect the battery cabinet types BP1000, BP3000 to the UPS using the supplied cable. The connection
scheme is shown in the figures below. Switch the circuit breaker on the battery cabinet to the ON position.
The UPS is now ready for operation.
NOTE: Battery charging times may be longer when using an external battery cabinet.
WARNING:
Fig. 13: Connection of Battery Extensions for devices Active 1000
WARNING: The connection of the external battery cabinet may only be done by qualified personnel
in accordance with the applicable safety regulations.
CAUTION: For the electrical installation, the maximum load capacity of the connection cable has to be taken into
account.
12
Cabinet
NA
2x (3 x 7. 2 Ah)
2x (8 x 7. 2 Ah)
2x (8 x 7. 2 Ah)
Batteries
Chloride Active and E-Series UPS User Manual
Battery Plug 1
Circuit Breaker
Battery Plug 2