Chloride LP061XHR User Instruction Manual

Linear plus rack-mount ups

Advertisement

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LP061XHR and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Chloride LP061XHR

  • Page 2: Important Safety Instructions

    F +44 (0) 2380 649994 F (847) 680-5124 www.chloride-na.com Entire contents copyright © 2007 Chloride Group PLC. All rights reserved. Reproduction in whole or in part without permission is prohibited. All information subject to change without notice. 913-610 @ Rev. B...
  • Page 4: Table Of Contents

    Introduction ......................................1 Registering Your UPS ..................................1 Technical Support ....................................1 FCC Compliance ....................................1 Safety Compliance ....................................1 Safety ........................................1 Intended Use ....................................1 Safety Notices ....................................2 Emergency ....................................3 Leakage Currents ..................................3 Radio Interference ..................................3 Batteries .......................................
  • Page 6: Introduction

    Please check with Chloride Service for assistance ordering, replacing, or disposing of batteries. Please check with Chloride Service before attempting to repair or return any Chloride product. If a Chloride UPS needs repair or replacement, Service will issue a Return Material Authorization (RMA) number along with instructions on how to return the UPS.
  • Page 7: Safety Notices

    • Even when all switches and interrupters are open, hazardous voltages are present within the UPS; any operation that requires protection panels to be opened and/or removed must be carried out by Chloride authorized technical personnel only.
  • Page 8: Emergency

    93/68/EEC. 89/336/EEC Directive of the council for adaptation of the legal regulations of the member states regarding electromagnetic compatibility, modified by directive 91/263/EEC, 92/31/EEC and 93/68/EEC. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 9: About The Operating Instructions

    Additional information regarding adherence to these directives is included in the appendices NSR and EMC of the EU Declaration of Conformity. If required, the EU Declaration of Conformity can be requested from Chloride. About the This manual contains information regarding the installation, operation and use of the Uninterruptible Power Supply (UPS) Linear Plus Rack-mount.
  • Page 10: Preparation For Use

    Taking into consideration the weight of the Linear Plus Rack-mount UPS/batteries as reported in Table 5 on page 9, it is necessary that the chosen cabinet be capable of supporting the weight of the unit / batteries. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 11: Inventory List

    Before beginning installation, be sure all parts are identified. Fig. 2: Rack Kit Installation 1. Using Fig. 2, assemble the left rail and right rail guides. Leave enough slack to permit final alignments in the rack. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 12: Installation

    UPS. For electrical installation, the nominal current rating of the source must be observed. The UPS must be connected to a suitably rated circuit. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 13: Installation Data

    48 A cos ϕ = 0.7 and 208 V General Over voltage category Protection class IP 20 Cooling Ventilator a. use battery type for replacement purpose also. No other type permitted Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 14: Cable Sizes And Current

    UPS be housed in earthed, metal conduits or that shielded cables be used. Routing of cables (e.g. power supplies, communication or data Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 15: Neutral Connection

    NOTE: The external battery cabinet shall be located adjacent to the UPS. When such an option is supplied by Chloride it comes complete with protection devices and correctly-sized cables. When batteries are sourced from other suppliers it is advised that Chloride be contacted for correct sizing of protection devices and interconnection cables.
  • Page 16: Terminal Blocks For Ups

    9. Battery socket open if UPS in parallel operation) 10. Strain relief 18. Terminals for backfeed control NOTE: Each external battery cabinet is supplied with one battery connection cable (16). The first Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 17: Connecting Mains

    The battery connection cable plug is keyed to the receptacles on the UPS and battery cabinet. Insure that the plug notch is correctly aligned with the receptacle guide when connecting the components together. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 18: Auxiliary Backfeed Protection

    • mains supply Normal and Safe • input switch Operating • rectifier/booster, inverter and charger • electronic bypass • paralleling contactor • RPO hardwired • backfeed protection logic • Battery racks are external. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 19: Ups Start-Up Procedure

    3. Switch the battery breaker to the closed ( | ) position. 4. Switch input breaker to “ON ’position ( | ). 5. The unit will go through a self-test. Wait for the yellow BYPASS LED to illuminate (approximately 15 seconds). Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 20: Ups Shutdown Procedure

    NOTE: To effect any action, the buttons must be pressed for at least 1 second! (Acceptance of the input Operating Elements is confirmed acoustically) Linear Plus The following is an explanation of the symbols printed on the front panel of the UPS: Rack-mount Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 21: Indication And Operating Elements

    This procedure is not often adopted. Although battery recharge starts immediately when the mains is re-established, it can take several hours to recharge the battery fully. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 22 For further information please refer to our publication about the Chloride connectivity solutions. Once the mains voltage returns, the UPS will restart in the preset mode. Depending on the installed software, the computer’s status before the mains failure can be re-established.
  • Page 23: Remote Power Off (Rpo)

    UPS switches (Input, Output and Battery) and carry out Switch-on procedure as described above “UPS Start-Up Procedure” on page 14). Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 24: Emergency Power Off (Esd Hardwired)

    1. Remove jumper from Parallel Terminals (S1, S2) from each UPS terminal block (each UPS). 2. Connect the input terminals of all UPS blocks to the mains distribution. See Figure 12 on page 20. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 25 In addition to the “LINE” and “BYPASS” LEDs the “LOAD” LED is now illuminated. After a few seconds the “INVERTER” LED is illuminated and the “BYPASS” LED is extinguished. The UPS is now in ON-LINE operation. The load is spread evenly across all the UPSs. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 26: Maintenance

    WARNING: Prior to starting the battery replacement, please read the entire instructions for important Replacement safety procedures. NOTE: To obtain new battery(ies), contact Chloride Technical Services at 847-816-6000, toll free at 800-879-5011 option 3. NOTE: The UPS cannot protect against power outages while the batteries are disconnected.
  • Page 27: Storage

    SIC to put slot COM The necessary communication software packages and interface cables are available as options. Serial Interface COM 3 The 9-pole SUB-D connector (pin contacts) contains RS 232 compatible signals. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 28 The interface COM 3 is galvanically isolated from primary UPS circuits. SGN at pin 5 Signal ground. RXD at pin 2 and TXD at pin 3 Receive and transmit RS 232 compatible signals. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 29: Optional Isolated Contacts Card

    This output provides an N/O contact between pins 2 and 5. The 2-5 contact closes when one of the alarms “AC FAIL,” “LOW BATT” or “BYPASS ACTIVE” is active or when the indication “ALARM” at the front-panel is on. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 30: Troubleshooting

    Interface on the PC is being used by accessing the interface on the PC; try another process or is defective. selecting a different serial interface. Interference on the data cable Lay cables differently. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 31 8 Charger fault Fault, 1 & OL Line, Bypass, Battery test Charge on, but battery <240V Bypass 9 RPO active Fault, 2 & 4 Any mode RPO hardware active No output Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 32 13 Back feed active Fault Line, Battery Battery circuit from inverter to bypass Units effected no 14 Parallel fault Fault, 3 & 4 Bypass, Line Fault of units in parallel output Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
  • Page 33 Troubleshooting Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...