Please check with Chloride Service for assistance ordering, replacing, or disposing of batteries. Please check with Chloride Service before attempting to repair or return any Chloride product. If a Chloride UPS needs repair or replacement, Service will issue a Return Material Authorization (RMA) number along with instructions on how to return the UPS.
• Even when all switches and interrupters are open, hazardous voltages are present within the UPS; any operation that requires protection panels to be opened and/or removed must be carried out by Chloride authorized technical personnel only.
93/68/EEC. 89/336/EEC Directive of the council for adaptation of the legal regulations of the member states regarding electromagnetic compatibility, modified by directive 91/263/EEC, 92/31/EEC and 93/68/EEC. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
Additional information regarding adherence to these directives is included in the appendices NSR and EMC of the EU Declaration of Conformity. If required, the EU Declaration of Conformity can be requested from Chloride. About the This manual contains information regarding the installation, operation and use of the Uninterruptible Power Supply (UPS) Linear Plus Rack-mount.
Taking into consideration the weight of the Linear Plus Rack-mount UPS/batteries as reported in Table 5 on page 9, it is necessary that the chosen cabinet be capable of supporting the weight of the unit / batteries. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
Before beginning installation, be sure all parts are identified. Fig. 2: Rack Kit Installation 1. Using Fig. 2, assemble the left rail and right rail guides. Leave enough slack to permit final alignments in the rack. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
UPS. For electrical installation, the nominal current rating of the source must be observed. The UPS must be connected to a suitably rated circuit. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
48 A cos ϕ = 0.7 and 208 V General Over voltage category Protection class IP 20 Cooling Ventilator a. use battery type for replacement purpose also. No other type permitted Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
UPS be housed in earthed, metal conduits or that shielded cables be used. Routing of cables (e.g. power supplies, communication or data Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
NOTE: The external battery cabinet shall be located adjacent to the UPS. When such an option is supplied by Chloride it comes complete with protection devices and correctly-sized cables. When batteries are sourced from other suppliers it is advised that Chloride be contacted for correct sizing of protection devices and interconnection cables.
9. Battery socket open if UPS in parallel operation) 10. Strain relief 18. Terminals for backfeed control NOTE: Each external battery cabinet is supplied with one battery connection cable (16). The first Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
The battery connection cable plug is keyed to the receptacles on the UPS and battery cabinet. Insure that the plug notch is correctly aligned with the receptacle guide when connecting the components together. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
3. Switch the battery breaker to the closed ( | ) position. 4. Switch input breaker to “ON ’position ( | ). 5. The unit will go through a self-test. Wait for the yellow BYPASS LED to illuminate (approximately 15 seconds). Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
NOTE: To effect any action, the buttons must be pressed for at least 1 second! (Acceptance of the input Operating Elements is confirmed acoustically) Linear Plus The following is an explanation of the symbols printed on the front panel of the UPS: Rack-mount Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
This procedure is not often adopted. Although battery recharge starts immediately when the mains is re-established, it can take several hours to recharge the battery fully. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
Page 22
For further information please refer to our publication about the Chloride connectivity solutions. Once the mains voltage returns, the UPS will restart in the preset mode. Depending on the installed software, the computer’s status before the mains failure can be re-established.
UPS switches (Input, Output and Battery) and carry out Switch-on procedure as described above “UPS Start-Up Procedure” on page 14). Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
1. Remove jumper from Parallel Terminals (S1, S2) from each UPS terminal block (each UPS). 2. Connect the input terminals of all UPS blocks to the mains distribution. See Figure 12 on page 20. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
Page 25
In addition to the “LINE” and “BYPASS” LEDs the “LOAD” LED is now illuminated. After a few seconds the “INVERTER” LED is illuminated and the “BYPASS” LED is extinguished. The UPS is now in ON-LINE operation. The load is spread evenly across all the UPSs. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
WARNING: Prior to starting the battery replacement, please read the entire instructions for important Replacement safety procedures. NOTE: To obtain new battery(ies), contact Chloride Technical Services at 847-816-6000, toll free at 800-879-5011 option 3. NOTE: The UPS cannot protect against power outages while the batteries are disconnected.
SIC to put slot COM The necessary communication software packages and interface cables are available as options. Serial Interface COM 3 The 9-pole SUB-D connector (pin contacts) contains RS 232 compatible signals. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
Page 28
The interface COM 3 is galvanically isolated from primary UPS circuits. SGN at pin 5 Signal ground. RXD at pin 2 and TXD at pin 3 Receive and transmit RS 232 compatible signals. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
This output provides an N/O contact between pins 2 and 5. The 2-5 contact closes when one of the alarms “AC FAIL,” “LOW BATT” or “BYPASS ACTIVE” is active or when the indication “ALARM” at the front-panel is on. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
Interface on the PC is being used by accessing the interface on the PC; try another process or is defective. selecting a different serial interface. Interference on the data cable Lay cables differently. Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
Page 31
8 Charger fault Fault, 1 & OL Line, Bypass, Battery test Charge on, but battery <240V Bypass 9 RPO active Fault, 2 & 4 Any mode RPO hardware active No output Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
Page 32
13 Back feed active Fault Line, Battery Battery circuit from inverter to bypass Units effected no 14 Parallel fault Fault, 3 & 4 Bypass, Line Fault of units in parallel output Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...
Page 33
Troubleshooting Chloride Linear Plus Series Rack-mount UPS User Instruction Manual...