Indicator and operating elements ..........GB - 12 Front side GB - 12 Rear side (upright devices) GB - 13 Models ACTIVE 700 and ACTIVE 1000 GB - 13 Models ACTIVE 2000 and ACTIVE 3000 GB - 14 Rear side (rack-mounting devices)
Cleaning GB - 36 Troubleshooting ................GB - 37 Technical data................GB - 39 Technical data for the models ACTIVE 700 to ACTIVE 3000 GB - 39 Technical data for the models ACTIVE 700-19 to ACTIVE 3000-19 GB - 42...
Page 7
COM 1 interface ................GB - 33 Rectification of errors ............... GB - 37 Electrical data (ACTIVE 700 to ACTIVE 3000) ........ GB - 39 General data (ACTIVE 700 to ACTIVE 3000) ........GB - 40 Mechanical data (ACTIVE 700 to ACTIVE 3000) ......GB - 40 Connections (ACTIVE 700 to ACTIVE 3000)........
Page 8
Warning Carefully read these instructions completely before installation in or- der to get accustomed with the correct handling of the CHLORIDE ACTIVE UPS. Otherwise, especially during installation and opera- tion, dangerous situations could arise.
CHLORIDE ACTIVE About these operating instructions About these operating instructions Device overview The CHLORIDE ACTIVE UPS devices are delivered with various nominal powers and in various housings. The following table provides an overview of all device variants: Housing Designation Order No.
About these operating instructions CHLORIDE ACTIVE Notices regarding the EU Declaration of Conformity The UPS devices CHLORIDE ACTIVE are in conformity with the following European directives: 73/23/EWG Directive of the council for adaptation of the legal regulations of the member states regarding electrical equipment for use within specific voltage limits, modified by directive 93/68/EWG.
CHLORIDE ACTIVE Safety Safety Intended use UPS devices serve as an uninterruptible power supply for connected loads. They are in compliance with all relevant safety regulations concerning infor- mation technology equipment, including electronic office machines for use in an office environment.
Page 12
• The sum of the leakage currents (current in the earth conductor) from the UPS and connected loads must not exceed the value of 3.5 mA for the models ACTIVE 700(-19), ACTIVE 1000(-19), ACTIVE 2000(-19) and ACTIVE 3000(-19). GB - 8 V02OCT/01 945040.066...
CHLORIDE ACTIVE Introduction Introduction These operating instructions contain all the information needed to install and operate the UPS. The uninterruptible power supply (UPS) is connected between mains and the electrical load. It protects the load from mains interruptions, especially power failures.
95-100 Table 4: Battery capacity • The most reliable method is, however, the use of the CHLORIDE UPS software. This can be used to continuously display the estimated remaining capacity of the battery prior to and during a mains failure. In addition, you can automate shutdown processes.
CHLORIDE ACTIVE Introduction In the event of an overload or an internal failure, the load is supplied without interruption directly by the mains supply via the automatic bypass. As soon as normal operating conditions are restored, the system automatically switches back to inverter operation.
Indicator and operating elements CHLORIDE ACTIVE Indicator and operating elements Front side The OVERLOAD indicator illuminates if the UPS is overloaded. The LOAD LED strip displays the load sta- tus of the UPS. The BYPASS indicator illuminates when the UPS delivers voltage supplied from the mains supply via the bypass.
CHLORIDE ACTIVE Indicator and operating elements Rear side (upright devices) Models ACTIVE 700 and ACTIVE 1000 COM 3 interface COM interface (optional) EXT. OUTLETS CONTROL interface USB interface Output sockets (AC OUTPUT) Mains connection (AC INPUT) Input fuse The fuse must only be changed when the device is switched off and the mains con- nection cable disconnected.
Indicator and operating elements CHLORIDE ACTIVE Models ACTIVE 2000 and ACTIVE 3000 EXT. OUTLETS CONTROL interface COM interface (optional) USB interface COM 3 interface Connection for battery extension Output sockets (AC OUTPUT) Input circuit breaker Mains connection (AC INPUT) Fig. 5: Rear side ACTIVE 2000 EXT.
The following figures show the UPS rack-mounting devices with the corre- sponding battery extensions. Notice No battery extensions can be connected to the ACTIVE 700-19 device. Models ACTIVE 700-19 and ACTIVE 1000-19 The following legend applies to figures Fig. 7 and Fig. 8:...
Indicator and operating elements CHLORIDE ACTIVE ACTIVE 1000-19 BPACTIVE1000-19 Fig. 8: Rear side, ACTIVE 1000-19 and battery extension Notice To connect the BPACTIVE1000-19 battery extension to the UPS ACTIVE 1000-19, use the separate cable (10) provided in the delivery contents.
CHLORIDE ACTIVE Indicator and operating elements Models ACTIVE 2000-19 and ACTIVE 3000-19 The following legend applies to figures Fig. 9 and Fig. 10: Mains connection (AC INPUT) Output sockets (AC OUTPUT) Input circuit breaker Interface COM 3 Interface USB Interface EXT. OUTLETS CONTROL...
Indicator and operating elements CHLORIDE ACTIVE ACTIVE 3000-19 BPACTIVE3000-19 Fig. 10: Rear side ACTIVE 3000-19 and battery extension Notice Included in the delivery contents for each BPACTIVE3000-19 battery extension are two battery extension cables. The first extension is connected to battery cable (10) of the UPS, each additional exten- sion is connected via the two aforementioned cables.
CHLORIDE ACTIVE Installation and commissioning Installation and commissioning Inspect the packaging and the device for damages. Should you find damages, please contact the delivery firm immedi- ately. Scope of delivery • This manual • UPS device • Connection cable with IEC 320 plug for the UPS input •...
Installation and commissioning CHLORIDE ACTIVE Mechanical fixing: Notice The devices must be fixed in the cubicle on both sides. Moreover, the front plate of the device must be screwed to the cubicle. The device must only be installed in horizontal position.
CHLORIDE ACTIVE Installation and commissioning Installing the UPS devices Notice When installing the rack-mounting devices (ACTIVE …-19), observe the additional information in chapter “Installation notes for rack- mounting devices” on page GB - 19. Unpack the device and place it on a solid, horizontal base.
Installation and commissioning CHLORIDE ACTIVE Commissioning the UPS devices Upon connection to mains, the batteries in the UPS are charged automati- cally. Before using the device, charge the batteries for 6 hours. You may use the UPS immediately without charging the batteries, however the specified maximum backup time (or discharge time) is not yet available.
UPS can be set to other values (see Table 7 on page GB - 39). The required software can be down- loaded from the CHLORIDE Internet page (http://www.chloridepow- er.com). Commissioning of an external battery extension The table below contains an overview of the designations of the battery extensions available for the UPS devices.
Installation and commissioning CHLORIDE ACTIVE Move the circuit breaker on the battery extension to the "ON" position. Notice When operating with an external battery extension, the charging process requires additional time. Connecting battery extension using the ACTIVE 1000 through ACTIVE 3000 as an example:...
CHLORIDE ACTIVE Installation and commissioning Now it is possible to switch to online operation by pressing the button. The device again tests the battery voltage (device beeps) and remains in bypass mode until a constant battery voltage is present. Notice...
Installation and commissioning CHLORIDE ACTIVE The following graphic shows the displays of the BATTERY LED strip possi- ble while setting the number of external battery extensions: Capacity in % Fig. 13: Number of external battery extensions Notice Upon conclusion of the adjustment procedure, the UPS is in bypass operation.
CHLORIDE ACTIVE Operational behaviour Operational behaviour Checking the operational readiness Now disconnect the UPS from the mains supply in order to check the mains backup function. If functioning properly and if batteries are charged, a signal tone should be audible in 4-second intervals. The "MAINS" LED (mains voltage) extin- guishes.
Operational behaviour CHLORIDE ACTIVE Initially, all elements of the "LOAD" LED strip illuminate. Beginning with the 1 - 35 % indicator, the remaining elements in this LED strip are extinguished one after the other. Afterward, the elements which correspond to the load state of the device illuminate.
CHLORIDE ACTIVE Operational behaviour Operating modes The UPS has three different operating modes when it is switched on. Normal operation (mains supply present) The loads are supplied directly from mains via the inverter. Fig. 14: UPS control panel in normal...
Operational behaviour CHLORIDE ACTIVE Battery operation (mains failure) In the event of a mains failure, the inverter supplies the loads without inter- ruption; the power is supplied by the battery. In this operating mode, an acoustical sound is emitted in intervals of approx.
CHLORIDE ACTIVE Interface description Interface description The UPS provides a COM 3 standard interface, a USB and an optional COM interface. These combine protocol-data transfer via a serial RS 232 inter- face or USB interface and the signal exchange via a contact interface (UPS interface).
Interface description CHLORIDE ACTIVE The COM 3 interface is electrically isolated from all other current circuits. • SGN at pin 5 This connection is the reference point for all signals. • RXD at pin 2 and TXD at pin 3 correspond to the normal assignment of an RS 232 interface.
CHLORIDE ACTIVE Interface description COM M ON AC FAIL AC FAIL BATT LOW BYPASS ACTIVE SUM ALARM INV SHUTDOWN COM 1 Fig. 18: COM 1 interface INV SHUTDOWN This input (pin 6: high signal +5 V … +12 V, t 1 s, pin 7: 0 V) makes it pos- sible for the control computer to switch off the UPS in the event of a mains failure.
Interface description CHLORIDE ACTIVE BYPASS ACTIVE (N.O. between 1 and 4) This signal is active when the device has been switched to bypass, the inverter is blocked and the power is supplied from the mains supply. SUM ALARM (N.O. between 8 and 4) This output is active when one of the messages "AC FAIL", "BATT LOW"...
CHLORIDE ACTIVE Maintenance Maintenance The UPS requires no maintenance by the user. When the usable lifetime of the battery has expired, the UPS and the battery connections eventually connected must be replaced by the responsible customer service represent- ative. As a rule, the usable lifetime of the battery is 4 years at 25°C ambient tem- perature;...
Maintenance CHLORIDE ACTIVE Cleaning Danger Risk of electrical shock during cleaning an operationally ready UPS Switch off the UPS by pressing the button and pull the mains plug out of the sock- When cleaning, do not use scouring agents or cleaning agents which are damaging to plastics.
CHLORIDE ACTIVE Troubleshooting Troubleshooting If, in spite of the high reliability of this device, problems should occur, please check the following points before contacting the responsible customer serv- ice representative: • Is the mains voltage present at the UPS input? •...
Page 42
Troubleshooting CHLORIDE ACTIVE Problem Possible cause Measure The fuse switch of the battery Move the fuse switch to the "ON" extension(s) is in the "OFF" position. position. The number of externally con- Correct settings (see “Commission- nected battery extensions was ing of an external battery extension”...
-15°C to + 40°C Perm. rel. humidity during operation 20% to 90%, no condensation perm. max. 3000m, from 1500m max. Installation altitude Ambient temperature = 35°C Table 8: General data (ACTIVE 700 to ACTIVE 3000) ACTIVE ACTIVE ACTIVE ACTIVE UPS model...
LED indicator on front side Signalling Acoustical alarm Message contacts, see SIC option Message Interface RS 232/USB Signal input, see SIC option Operation Interface RS 232/USB Table 11: Other data (ACTIVE 700 to ACTIVE 3000) GB - 41 945040.066 V02OCT/01...
-15°C to + 40°C Perm. rel. humidity during operation 20% to 90%, no condensation perm. max. 3000m, from 1500m max. Installation altitude Ambient temperature = 35°C Table 13: General data (ACTIVE 700-19 to ACTIVE 3000-19) ACTIVE ACTIVE ACTIVE ACTIVE UPS model...
3000-19 LED indicator on front side Signalling Acoustical alarm Signalling contact +5V … +12V (SIC) Message Signal input +5V … +12V (SIC) Operation Interface RS 232 Table 16: Other data (ACTIVE 700-19 to ACTIVE 3000-19) GB - 44 V02OCT/01 945040.066...
CHLORIDE ACTIVE Technical data Usable Battery lifetime Ambient temperature Fig. 19: Usable battery lifetime The diagram shows the typical usable lifetimes of the batteries used in the UPS devices (only as a function of the ambient temperature of the devices).
ACTIVE Watt 700(-19) 1000(-19) 1000(-19) + 1 BP 1000(-19) + 2 BP 14,5 10,5 1000 Table 17: Backup times ACTIVE 700(-19) and ACTIVE 1000(-19) ACTIVE 2000 ACTIVE 2000 ACTIVE 2000 + 1 BP + 2 BP Watt ACTIVE ACTIVE ACTIVE...
CHLORIDE ACTIVE Technical data ACTIVE 3000 ACTIVE 3000 ACTIVE 3000 + 1 BP + 2 BP Watt ACTIVE ACTIVE ACTIVE ACTIVE ACTIVE 3000-19 3000-19 3000-19 3000-19 3000-19 + 1 BP + 2 BP + 3 BP + 4 BP + 5 BP...
Page 52
Technical data CHLORIDE ACTIVE GB - 48 V02OCT/01 945040.066...
Page 53
40023 Castel Guelfo Bologna Italy Telephone: +39 054 2632 111 Facsimile: +39 054 2632 120 italy.sales@chloridepower.com AUSTRALIA Chloride Hytek PTY LTD Units C1A and C1B Centrecourt Business Park 25-27 Paul Street North North Ryde NSW 2113 Australia Telephone: +61 2 9888 1266 Facsimile: +61 2 9888 1966 australia.sales@chloridepower.com...
Page 54
CHLORIDE ADDRESSES CHLORIDE ACTIVE Chloride Industrial Systems 30 Avenue Montgolfier - BP 90 F-69684 Chassieu Cedex France Telephone: +33 4 7840 1356 Facsimile: +33 4 7890 5890 industrial.sales@chloridepower.com Chloride Telecom Systems ZA Les Rolandières 35120 Dol de Bretagne France Telephone: + 33 299 48 2068 Facsimile: + 33 299 48 3394 com-ce@saed.com...
Page 58
CHLORIDE ADDRESSES CHLORIDE ACTIVE Latin America Chloride Power Protection Latin America Rua Arizona 1349 Brooklin Novo Sao Paulo CEP 04567-002 Brazil Telephone: +55 11 5505 4661 Facsimile: +55 11 5505 4832 latinamerica.sales@chloridepower.com Asia Pacific Chloride Power Protection 80 Marine Parade Road...
Herausgegeben von / Published by / Publié par / Publicado por / Pubblicato da / Editado por CHLORIDE SILECTRON Via Fornace 30 40023 Castel Guelfo Bologna Italy Bestell-Nr. / Order No. / No. de réf. / Nº de pedido / Codice di ord. N° / Nº de encomenda 945040.066...