Page 2
Chapter 1 Safety Precautions Before Supplying Power to the Inverter Warning The main circuit must be correctly wired. For single phase supply use input terminals (R/L1, T/L3) and for three phase supply use input terminals (R/L1, S/L2, T/L3). Terminals U/T1, V/T2, W/T3 must only be used to connect the motor. Connecting the input supply to any of the U/T1, V/T2 or W/T3 terminals will cause damage to the inverter.
Page 3
Do not connect a braking resistor directly to the DC terminals P (+) and N (-), otherwise fire may result. Use wire gauge recommendations and torque specifications. (See Wire Gauge and Torque Specification in section 3.6) Never connect input power to the inverter output terminals U/T1, V/T2, W/T3. ...
Page 4
Carefully check the performance of motor or machine before operating at high speed, otherwise Injury may result. Note the parameter settings related to the braking unit when applicable. Do not use the inverter braking function for mechanical holding, otherwise injury may result.
Page 5
Chapter 2 Environment and Installation 2.1 System Diagram ~ ~ ~ Power supply: Power Supply Make sure the correct voltage is applied to avoid damaging the inverter. Molded Molded-case circuit breaker (MCCB) or fused disconnect: Circuit A molded-case circuit breaker or fused disconnect must be installed Breaker between the AC source and the inverter that conforms to the rated voltage and current of the inverter to control the power and protect the...
Page 6
2.2 General Wiring Diagram (For Standard H & C type) Notes: *1: Models 200V 1 ~ 25HP and 400V 1 ~ 40HP or lower ratings have a built-in braking transistor. To use this braking transistor a braking resistor can be connected between B1 and B2. *2: Use SW3 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function digital input terminals S1~S8.
Page 7
2.3 General Wiring Diagram (For Enhanced E & G type) Notes: *1: Models 200V 1 ~ 25HP and 400V 1 ~ 30HP or lower ratings have a built-in braking transistor. To use this braking transistor a braking resistor can be connected between B1 and B2. *2: Use SW6 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function digital input terminals S1~S8.
Page 8
*9: Only the model 200V 3~40HP and 400V 5~75HP provide P1 and P2 terminal, for external DCL connected. P1 and P2 are short-circuited before shipping out from the factory. 2.4 General Power Terminals (For Standard H & C type) 200V: 1 ~ 25HP 200V: 30 ~ 150HP 400V: 1 ~ 40HP Terminal...
Page 10
Type Terminal Terminal Function Signal Level / Information signal Multi-function analog output terminals . can use (Load < 500Ω) SW6 to switch voltage or current input (0~10V / 4- PWM Frequency: 10KHz 20mA output) Analog signals ground terminal Pulse output, Band width 32KHz, only above 200V Max.
Page 11
2.7 User (Control) Terminals (For Enhanced E & G type) 200V: 1 ~ 2 HP, 400V: 1 ~ 3HP 200V: 3 ~ 40 HP, 400V: 5 ~ 75HP 200V: 50 ~ 150 HP, 400V: 100 ~ 425HP Description of User Terminals Type Terminal Terminal Function...
Page 12
Type Terminal Terminal Function Signal Level / Information signal Analog signals ground terminal ---- L: from 0.0 to 0.5V H: from 4.0 to 13.2V Max. Frequency: 0 - 32KHz Pulse command input, Pulse Built-in pull-up resistance. Bandwidth: 32KHz input When open collector input signal is used, it is not required to connect resistance.
Page 13
2.8 Cooling Fan Supply Voltage Selection (400V class) The inverter input voltage range of the A510s 400V class models ranges from 380 to 480Vac. In these models the cooling fan is directly powered from the power supply. Inverter models A510s-4150/ 4175/ 4215/ 4270/ 4300/ 4375/ 4425 requires the user to select the correct jumper position based on the inverter input voltage ("440V"...
Page 14
Chapter 3 Parameters Parameter group Group Name Basic Parameters Group 00 V/F Control Parameters Group 01 IM Motor Parameters Group 02 External Digital Input and Output Parameters Group 03 External Analog Input and Output Parameters Group 04 Multi-Speed Parameters Group 05 Automatic Program Operation Parameters Group 06 Start /Stop Parameters...
Page 15
Group 00: Basic Parameters Group 00: Basic Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 0: V/F 2: Terminal Command 1: V/F+PG UP/DOWN 2: SLV Control Mode Communication 00-00 3: SV Selection Control (RS-485) 4: PMSV 4: Pulse Input 5: PMSLV...
Page 16
Group 00: Basic Parameters Group 00: Basic Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 8: Manual Pulse *Jog Generator 00-18 0.00~599.00 6.00 Frequency (MPG) (Note4) 9: Band Saw 00-19 Acceleration 0.1~0600.0 10: Stamping Time Press Modified...
Page 17
*** If parameter 00-27 is set to ND mode, group 02 motor Group 01: V/F Control Parameters 1 parameter will automatically adjust to more than 1 Parameter Attrib Code Setting Range Default class of it. Name If parameter 00-27 is set to HD mode, group 02 motor 1 Compensatio Mode 0 parameter will automatically adjust to the same class...
Page 18
Group 01: V/F Control Parameters Group 02: IM Motor Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Motor 2 02-16 Reserved KVA: The default value of this parameter will be 02-18 changed by different capacities of inverter. 200V: 50~240 No-Load Group 02: IM Motor Parameters...
Page 19
Group 03: External Digital Input and Group 03: External Digital Input and Output Parameters Output Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 1: 2-Wire 19: Speed Sequence (ON: Search 1 (from Reverse Run the maximum Command) frequency)
Page 20
Group 03: External Digital Input and Group 03: External Digital Input and Output Parameters Output Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 43: PG Integral S4 Type xxx1b: S1 B Reset Selection Contact 44: Mode xx0xb: S2 A...
Page 21
Group 03: External Digital Input and Group 03: External Digital Input and Output Parameters Output Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 46~49: Reserved 15~17: Reserved 50: Frequency 18: PLC status Detection 3 (≧ 19: PLC Control 03-44+03-45) Contact...
Page 22
Group 03: External Digital Input and Group 03: External Digital Input and Output Parameters Output Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 03-11, 03-12 Frequency Photo-coupler Range and 3: Output Output definition are the Frequency 03-21 Selection...
Page 23
Group 03: External Digital Input and Group 04: External Analog Input and Output Parameters Output Parameters Parameter Parameter Attrib Attrib Code Setting Range Default Code Setting Range Default Name Name Level 6 9: Jump Frequency 4 Current 03-53 0.0~999.9 Note4 Agree Level 2 10: Added to AI1 11: Positive...
Page 24
Group 04: External Analog Input and Group 05: Multi-Speed Parameters Output Parameters Parameter Attrib Code Setting Range Default Name Parameter Attrib Code Setting Range Default 0: Acceleration Name and deceleration 14: Reserved Acceleration time are set by 15: ASR Output 00-14 ~ 00-24 05-00 Deceleration...
Page 25
Group 05: Multi-Speed Parameters Group 05: Multi-Speed Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name of Multi Time Setting Speed 0 of Multi Speed 7 Deceleration Time Setting Acceleration 05-18 0.1~6000.0 10.0 of Multi Time Setting 05-33 0.1~6000.0...
Page 26
Group 05: Multi-Speed Parameters Group 06: Automatic Program Operation Parameters Parameter Attrib Code Setting Range Default Name Parameter Attrib Code Setting Range Default Acceleration Name Time Setting *Frequency 05-47 0.1~6000.0 10.0 of Multi Setting of 06-01 0.00~599.00 5.00 Speed 15 Operation- Deceleration Stage 1...
Page 27
Group 06: Automatic Program Operation Group 06: Automatic Program Operation Parameters Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name *Frequency of Speed- Setting of Stage 13 06-15 0.00~599.00 5.00 Operation- Operation Stage 15 Time Setting 06-30 0.0~6000.0...
Page 28
Group 06: Automatic Program Operation Group 07: Start /Stop Parameters Parameters Parameter Attrib Code Setting Range Default Name Parameter Attrib Code Setting Range Default Braking Time Name at Stop Speed-Stage 0: Deceleration Operation to Stop 0: Stop Direction 1: Coast to Stop 06-45 1: Forward Selection of...
Page 29
Group 07: Start /Stop Parameters Group 07: Start /Stop Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Start Selection 0: Start with Current Limit after Fault speed search 07-27 PM Speed 0: Disabled during SLV 1: Normal start Switching...
Page 30
Group 08: Protection Parameters Group 08: Protection Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Stall 2: Start to Detect HD:160 when the Prevention 08-03 30~200 Operation is Level in ND:120 Begun. Operation 0: Deceleration 08-04 Reserved...
Page 31
Group 08: Protection Parameters Group 08: Protection Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Time in Prevention Operation Limit Ground Fault 0: Disable 08-23 (GF) 08-42 Protection 0.1~10.0V 1: Enable Selection Level 0: Deceleration PTC Restart 08-43...
Page 32
Group 09: Communication Parameters Group 08: Protection Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Tolerance Frequency (01- Count Fire Mode 09-09 Waiting Time 5~65 0: Forward 08-59 Motor Note4 09-10 Reserved 1: Reverse Direction 0: Disable 09-11 Bluetooth...
Page 33
Group 10: PID Parameters Group 10: PID Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Differential 10-32 Reserved 10-07 0.00~10.00 0.00 Time (D) Maximum 10-33 Value of PID 1 ~ 10000 10-08 Frequency 0.00~599.00 Note2 Feedback...
Page 34
Group 11: Auxiliary Parameters * If the maximum output frequency of motor is over Parameter Attrib 300HZ, the frequency resolution is changed to 0.1Hz Code Setting Range Default Name Manual Energy 11-18 Saving 0.0~599.0 0.00 Frequency Group 11: Auxiliary Parameters 0: Automatic energy saving Parameter...
Page 35
Group 11: Auxiliary Parameters Group 11: Auxiliary Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Frequency Zero-servo 11-50 0~4096 11-36 Gain of OV 0.000~1.000 0.050 Count Prevention Braking 0: Disable **Frequency 11-51 Selection of 1: Enable 11-37 Limit of OV...
Page 36
Group 11: Auxiliary Parameters Group 11: Auxiliary Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 0: Mode1 11-82 OVP4 Gain 0~256 Selection of 1: Mode2 11-62 Preventing *: Refer to the attachment 1 in our instruction manual.. Oscillation 2: Mode3 ** If the maximum output frequency of motor is over...
Page 37
Group 12: Monitoring Parameters Group 12: Monitoring Parameters Setting Range Setting Range Parameter Attrib Parameter Attrib Code Default Code Default Name Name Speed with the current fault First Decimal If LED enters Place (xxxx.x) this parameter, 3: Display Line Frequency it only allows 12-16 Speed with the...
Page 38
Group 12: Monitoring Parameters Group 12: Monitoring Parameters Setting Range Setting Range Parameter Attrib Parameter Attrib Code Default Code Default Name Name Display the values of 20-27) current Al2 input Display input (0V or 4mA error of the PID corresponds to controller (PID 12-26 AI2 Input 0%, 10V or...
Page 39
Group 12: Monitoring Parameters Group 12: Monitoring Parameters Setting Range Setting Range Parameter Attrib Parameter Attrib Code Default Code Default Name Name Previous Three Display Warning recent warning 12-48 Fault previous three Messages messages Messages fault messages Display the Previous Previous Four Display previous...
Page 40
Group 13: Maintenance Parameters Group 13: Maintenance Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Inverter /575V) 8: PLC 13-00 Capacity ---- initialization Selection 9: 2 wire Initialization Software 13-01 0.00-9.99 (60Hz)(230/460V) Version 10: 3 wire 0: Disable to Initialization...
Page 41
Group 13: Maintenance Parameters Group 13: Maintenance Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Exhibit Fault History twenty one Previous five 13-25 Previous five Note1 Fault History Fault History Fault History Exhibit Previous Exhibit Previous...
Page 42
Group 14: PLC Setting Parameters Group 15: PLC Monitoring Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name (Mode7) 14-08 T5 Set Value 1 0~9999 Note6 T5 Set Value 2 15-06 T4 Current Value 1 0~9999 14-09 0~9999 Note6...
Page 43
Group 16: LCD Function Parameters Group 16: LCD Function Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name monitored item represents the displays in the display of second line. X.XXX at (default is 100%. output 0: without frequency)
Page 44
Group 16: LCD Function Parameters Group 16: LCD Function Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name inverter 4:Thu parameters and 5:Fri 16-29 P4 Stop Date Note8 save to the 6:Sat operator. 7:Sun 0: Keep 0: Disable Selection of...
Page 45
Group 16: LCD Function Parameters Group 17: Automatic Tuning Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Frequency 60.0 Rotation Motor Rated xx0xb: RTC 17-05 0~24000 Speed Run2 Pole Number of Forward 17-06 2~16 (Even) Motor Rotation...
Page 46
*: It is suggested that HD/ ND mode (00-27) and Group 19: Wobble Frequency Parameters application presets (00-32) be selected first Parameter Attrib Code Setting Range Default Name before motor performs auto-tuning. Frequency Cycle Note: The value of mode selection of automatic Wobble tuning is 6 (Static Auto-tuning Combination).
Page 47
Group 20: Speed Control Parameters Group 20: Speed Control Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Feedback 1 1: Forward as Clockwise Low-pass Filter Rotation Time Constant 20-14 1~1000 of Speed PG Pulse 20-29 001~132 Feedback 2...
Page 48
Group 21: Torque And Position Control Group 21: Torque And Position Control Parameters Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Torque Limit Number of Section 5 Forward 21-07 Regenerative 0~300 The Command Torque Limit of Rotation 21-22...
Page 49
Group 21: Torque And Position Control Group 22: PM Motor Parameters Parameters Parameter Attrib Code Setting Range Default Parameter Attrib Name Code Setting Range Default Name PM Motor’s Number of 22-05 Maximum 6~60000 1500 Section 12 Rotation Speed The Command PM Motor of Rotation 22-06...
Page 50
Group 22: PM Motor Parameters Group 22: PM Motor Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name and Loop Control Adjustment (for 2: Full Closed PMSV Tuning) Loop Control 3: Rotation 5~120 (Note7) Voltage Auto-tuning (22-25=2 or 22-...
Page 51
Use one of the following methods to restart: Group 22: PM Motor Parameters 1. Set one of multi-function digital input Parameter Attrib Code Setting Range Default terminals (03-00, 03-07) to 17 (Fault reset); Name activate input Preliminary DC 22-39 0~20.00 0.10 2.
Page 52
LED display Possible solutions LED display Possible solutions Reduce input voltage to Check load / application. comply with the input voltage requirements or Revise the sequence install an AC line reactor Switch for Motor1/Motor2 control and switch motor to lower the input voltage.
Page 53
LED display Possible solutions LED display Possible solutions CF00 Operator Disconnect the operator Communication and then reconnect. Error Replace the control board External fault (S2) CF01 Operator Disconnect the operator Communication and then reconnect. External fault Error 2 ...
Page 54
does not accept a run command until the LED display Corrective action programming error is corrected. Note: When a warning or self- diagnostic error is active the warning or error code will flash on Check over torque the keypad. When the RESET key is pressed, (flash) detection parameters over torque...
Page 55
LED display Corrective action LED display Corrective action over current (flash) protection level External Check load and duty baseblock cycle operation. over current (flash) protection level External Check load and duty baseblock cycle operation. Retry (flash) Check ASR parameters (flash) ...
Page 56
LED display Corrective action LED display Corrective action Install PG feedback (S5) SE07 card. PG card error Check control mode. Set right type for PM Encoder Type (22-08) EF6 ( flash ) and power on again. External fault SE08 (S6) PM Motor...
Page 57
LED display Corrective action 4.4 Auto-tuning Error When a fault occurs during auto-tuning of a PArEr Parameter standard AC motor, the display will show the Please refer to our setting error “AtErr” fault and the motor stops. The fault instruction manual for correct setting information is displayed in parameter 17-11.
Page 58
Table 4.4, for fault information during tuning, cause and corrective action. Table 4.4 Auto-tuning fault and corrective actions for PM motor Error Corrective action Check the motor tuning Magnetic pole data (22-02). alignment tuning Check inverter capacity failure (static). ...
Page 101
Main Circuit Terminal Wiring UL approval requires crimp terminals when wiring the inverter’s main circuit terminals. Use crimping tools as specified by the crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the insulation cap. The table below matches inverter models with crimp terminals and insulation caps.
Page 103
Type 1 During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used. 690V 80A...
Page 104
Motor Over-temperature Protection Motor over temperature protection is not provided. Motor over-temperature protection shall be provided in the end use application. ■ Field Wiring Terminals All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections that are to be made to each terminal and indicate that copper conductors, rated 75°C are to be used.
Page 105
Préface Le produit est un lecteur conçu pour commander un moteur à induction triphasé. lire attentivement ce manuel pour garantir le bon fonctionnement, la sécurité et pour se familiariser avec les fonctions d'entraînement. Le lecteur est un appareil électrique / électronique et doit être installé et géré par un personnel qualifié...
Page 106
Coupez toujours l'alimentation électrique avant de procéder à l'installation d'entraînement et le câblage des terminaux utilisateurs. Le câblage doit être effectué par un personnel qualifié / électricien certifié. Assurez-vous que le lecteur est correctement mis à la terre. (220V Classe: impédance de mise à...
Page 107
pourrai se déclencher et ainsi endommager le lecteur. Les opérations peuvent commencer soudainement si une alarme ou un défaut est réarmé avec un ordre de marche active. Assurez-vous qu'un ordre de marche est actif lors de la réinitialisation de l'alarme ou de défaut, autrement des accidents peuvent se produire.