5.6.1 Mains water pressure boosting
In some countries, boosting from the city water mains is
prohibited. Please follow local regulations regarding this
application.
2
7
10
5
3
Mains water pressure boosting, SCALA2
Pos. Description
1
Highest tapping point
2
Pipe hangers and supports
3
Isolating valves
4
Flexible hoses
5
Bypass valve
Optional pressure-reducing valve on the inlet side if the
6
pressure can exceed 10 bar (145 psi).
Optional pressure-relief valve on the outlet side if the instal-
7
lation cannot withstand a pressure of 6 bar (87 psi).
Drip tray. Install the pump on a small stand to prevent the
8
ventilation holes from being flooded.
9
Pressure gauge
10
Mains water pipe
1
3
9
4
6
2
8
5.6.2 Suction from a well
2
1
5
6
Suction from a well
Pos. Description
1
Highest tapping point
2
Isolating valve
3
Flexible hoses
4
Pipe support
Inlet filter.
If the water may contain sand, gravel or other debris,
5
please install a filter on the inlet side to protect the pump
and installation.
6
Foot valve with strainer (recommended).
H1
Maximum suction lift is 8 m (26 ft).
H2
Inlet pipe must be submersed at least 0.5 m (1.64 ft).