S&A CWFL-4000 User Manual page 14

Dual temperatureanddual pump industrialchiller
Hide thumbs Also See for CWFL-4000:
Table of Contents

Advertisement

Slave response
Function code
Register address
Register value
Error
Error code
Exception code
For example: if the host's sending address is 1, requests command of writing data
00 03 to register 2. Host send: 01 06 00 02 00 03 XX YY, thereinto, 01 as slave
address, 06 as function code, 00 02 as register address, 00 03 as written data and XX
YY as verification code.
Slave response: 01 06 00 02 00 03 XX YY, thereinto, 01 as slave address, 06 as
function code, 00 02 as register address, 00 03 as written data and XX YY as CRC
verification code.
If there is data error or communication exception, send 01 86 02 XX YY.
3. Read only parameter(sensor, current)
Register
Description
address
Room temp. sensor
0x0100
temperature
Water temp. sensor
0x0101
temperature(Low temp)
Water temp. sensor
0x0102
temperature(High temp)
Compressor exhaust
0x0103
temperature
0x0104
Flow of the first waterway
0x0105
Flow of the second waterway
0x0105
Conductivity
Compressor current
0x0106
(Three-phase average)
0x0107
Low temp. water pump current
0x0108
High temp. water pump current
1 bytes
0x86
2 bytes
From 0x0400 to 0x044a
2 bytes
From 0x000 to 0xffff
1 bytes
0x86
1 bytes
01 or 02 or 03 or 04
Read-only
Range
-25 ~ 100
-25 ~ 100
-25 ~ 100
-25 ~ 140
0.1-200
0.1-200
0.1-500
0-50
0-50
0-50
Default
Unit
L/Min
L/Min
μs/cm
A
A
A
14
CWFL-4000 Series
Data
Symbol
resolution
0.1/bit
yes
0.1/bit
yes
0.1/bit
yes
0.1/bit
yes
0.1/bit
yes
0.1/bit
yes
0.1/bit
yes
0.1/bit
yes
0.1/bit
yes
0.1/bit
yes