S&A CWFL-4000 User Manual page 10

Dual temperatureanddual pump industrialchiller
Hide thumbs Also See for CWFL-4000:
Table of Contents

Advertisement

High temp. system
E02
flow alarm
Ultra-high room
E03
temp.alarm
Low temp. system
E04
ultra-low water temp
alarm
Low temp. system
E05
ultra-high water temp
alarm
High temp. system
E06
ultra-low water temp
alarm
High temp. system
E07
ultra-high water temp
alarm
Wrong phase and
E08
lacking phase alarm
Compressor overload
E09
alarm
Low temp. water
E10
pump overload alarm
High temp. water
E11
pump overload alarm
Refrigeration system
E12
high pressure alarm
Refrigeration system
E13
low pressure alarm
Room temp. sensor
E14
failure alarm
Low temp. system
E15
water temp. sensor
failure alarm
High temp. system
E16
water temp. sensor
failure alarm
Ultra-high conductivity
E17
alarm
Ultra-low conductivity
E18
alarm
E02 shown with
Heater of the high temp. system
alarm sound
E03 shown with
Each refrigeration part runs under
alarm sound
The compressor, condenser fans
E04 shown with
and heater of the high/low temp.
alarm sound
E05 shown with
Each refrigeration part runs under
alarm sound
E06 shown with
Each refrigeration part runs under
alarm sound
E07 shown with
Heater of the high temp. system
alarm sound
The water pump, compressor,
E08 shown with
condenser fans and heater of the
alarm sound
high/low temp. system shut down
The compressor, condenser fans
E09 shown with
and heater of the high/low temp.
alarm sound
The water pump, compressor,
E10 shown with
condenser fans and heater of the
alarm sound
high/low temp. system shut down
E11 shown with
The water pump and high temp.
alarm sound
E12 shown with
The compressor and condenser fans
alarm sound
E13 shown with
The compressor and condenser fans
alarm sound
Switched to constant temp. mode
E14 shown with
and each refrigeration part runs
alarm sound
The water pump, compressor,
E15 shown with
condenser fans and heater of the
alarm sound
high/low temp. system shut down
E16 shown with
High temp. system water pump and
alarm sound
E17 shown with
Each refrigeration part runs under
alarm sound
E18 shown with
Each refrigeration part runs under
alarm sound
10
shut down
usual procedures
system shut down
usual procedures
usual procedures
shut down
system shut down
system heater shut down
shut down
shut down
under usual procedures
heater shut down
usual procedures
usual procedures
CWFL-4000 Series
Automatic clearing
Automatic clearing
Automatic clearing
Automatic clearing
Automatic clearing
Automatic clearing
Manual clearing
Manual clearing
Manual clearing
Manual clearing
Manual clearing
Automatic clearing
Automatic clearing
Automatic clearing
Automatic clearing
Automatic clearing
Automatic clearing