(FireProtect Plus) is a wireless indoor �re detector with an in-built buzzer and a battery, ensuring up to 4 years of autonomous operation. FireProtect can detect smoke and rapid temperature increase. Aside from these functions, FireProtect Plus additionally can alert of dangerous CO level.
The system noti�es the user of all events through push noti�cations, SMS, and calls (if activated). The Ajax security system can be connected to a central monitoring station of a security company. Buy �re detector FireProtect Functional Elements 1. Siren hole 2.
Page 3
60°С), the detector registers temperature increase, which triggers a �re alarm. The life span of the FireProtect Plus detector lasts up to 7 years (up to 10 years for the FireProtect ). In the event of a detector failure, you will receive a corresponding noti�cation —...
Page 4
2. Through the Ajax app. In case of �re alarm, you will see a pop-up message in Ajax app suggesting to turn off the built-in sirens. 3. Using the KeyPad KeyPad Plus (if Interconnected FireProtect Alarms feature is enabled). To turn off the built-in sirens in case of �re alarm, press the “*”...
Page 5
Fire Alarm command for this button in the KeyPad/KeyPad Plus settings. If smoke and/or temperature levels do not restore to normal values, in 10 minutes, the FireProtect/FireProtect Plus turns on the siren again. Connecting the Detector to the Ajax Security System...
Page 6
3. Tap Add — the countdown will start. 4. Switch on the device. To make sure that the detector is on, press the on/off button — the logo will light up red for a second. For detection and pairing to occur, the detector should be located within the coverage area of the wireless network of the hub (at a single protected object).
Page 7
The smoke detector always operates in the active mode. When connecting FireProtect to third party security systems, it is appropriate to place it in a permanently active protection zone. States 1.
Page 8
Firmware Detector �rmware version Device ID Device identi�er Settings 1. Devices 2. FireProtect | FireProtect Plus 3. Settings Setting Value First �eld Device name, can be edited Selecting the virtual room to which the device is...
Page 9
CO concentration is only) dangerous Switches the device to the signal strength test Jeweller Signal Strength Test mode FireProtect Self Test Starts FireProtect selftest Allows the user to disconnect the device without removing it from the system. Two options are available: •...
Page 10
5. Go to the Fire detectors settings menu and activate the Interconnected FireProtect Alarms option Interconnected alarms are supported by FireProtect and FireProtect Plus detectors with �rmware versions 3.42 and later. Please note that when you turn on the interconnected alarms, you cannot set the hub–detector ping interval (Jeweller settings) of more than 48...
Page 11
4. An alarm con�rmation event is sent to the monitoring station and security system users, and the system starts the interconnected alarm for �re detectors if: The interconnected alarm delay time has passed, and the triggered detector is • still registering an alarm. During the delay of the interconnected alarms, the triggered detector reports a •...
Page 12
During the interconnected alarm delay, another �re detector in the system • raised an alarm. To give more time to eliminate the cause of false triggering of the detector, the user can delay the propagation of the interconnected alarm for another 10 minutes: Through Ajax apps. •...
Page 13
By pressing the KeyPad/KeyPad Plus function button (in the interconnected �re • alarm muting mode). By pressing the Button in the interconnected �re alarm muting mode. • • By eliminating the cause of the alarm (�re detectors at the facility no longer detect an alarm).
Page 14
3. If after 30 seconds the detector still detects a threat, an alarm is sent to the hub. Setting the Residential �re alarm system Residential �re alarm system is an Ajax system feature that de�nes user and device rights to mute the interconnected alarms of �re detectors.
Three short sound signals per 90 sec — both batteries low Performance testing The Ajax security system allows conducting tests for checking the functionality of connected devices. The tests do not start straight away but within a period of 36 seconds when using the standard settings.
Installation Selecting the Location The location of the detector depends on its remoteness from the hub, and obstacles hindering the radio signal transmission: walls, �oors, large objects inside the room. The device developed only for indoor use. If the signal level is low (one bar), we cannot guarantee the stable operation of the detector.
Page 17
Before installing the detector, make sure that you have selected the optimal location that follows the guidelines of this manual! 1. Fix the SmartBracket panel on the ceiling using bundled screws. If you use any other attachment tools, make sure that they do not damage or deform the attachment panel.
Page 18
2. nearby any metal objects or mirrors causing attenuation or screening of the signal; 3. at any places with fast air circulation (air fans, open windows or doors); 4. closer than a meter to the cooking surface; 5. inside premises with the temperature and humidity beyond the range of permissible limits;...
— three short signals. • Keep new and used batteries away from children. Do not ingest battery, Chemical Burn Hazard. How long Ajax devices operate on batteries, and what affects this Battery Replacement Tech Specs...
Page 20
Maximum RF output power Up to 20 mW Radio signal modulation GFSK Up to 1,300 m (any obstacles absent) Radio signal range Learn more 2 × CR2 (main batteries), CR2032 (backup Power supply battery), 3 V Battery life Up to 4 years Indoors Installation method Operating temperature range...
6. Quick Start Guide Warranty Warranty for the “AJAX SYSTEMS MANUFACTURING” LIMITED LIABILITY COMPANY products is valid for 2 years after the purchase and does not apply to the pre-installed battery. If the device does not work correctly, you should �rst contact the support service —...
Need help?
Do you have a question about the FireProtect and is the answer not in the manual?
Questions and answers