CD Automation REVO REVEX3PH User Manual page 32

Table of Contents

Advertisement

REVEX
3PH from 120A to 210A
9.4.3 Advanced Setup Menu
This section describes each item on the advanced setup menu. Use this menu to configure the power
switching, closed loop control of power and adjustable settings for data logging and heater bakeout. The
password to access this menu is 10.
Parameter Name
Firing Type
Choose the firing mode
Parameter Name
Min Cycles
Set the minimum number of On
cycles and off cycles for burst firing
Cycle time
Set the duration of one on-off cycle
in increments of 50mSec.
Applies to zero crossing
Feedback
Choose the feed-back type
Description
Option
Zero Cross
Burst fire
DEFAULT: Burst Fire
Description
Option
Voltage squared
None
No feed-back
Current squared
Voltage
Voltage
Current
Current
Power
Power
External
External signal via analog input 2
DEFAULT: None
Value
1
3
3
Default
8
0 to 999.9
60
0 to 12,75
(3 sec)
1
Description
32
User's manual
Modbus
Default
Address
3
18
Modbus
Range
Unit
Address
20
0 to 255
24
sec)
19
Value
0
1
2
32
64
128
256
1
Par.
Type
Read
Write
Par.
Type
Read
Write
Read
Write
Read
Write