• Before replacing any components within the SCB3000, power must be disconnected from the SCB3000 and the newly Solar Communication Box replaced components must be ensured to meet the requirements for use of the SCB3000, and GOODWE will not be liable for any personal harms or warranty claims arising from noncompliance with this instruction.
4 Equipment Installation Label Description 4.1 Installation Instructions Three-phase AC and protective ground wiring port (with a waterproof cap) L1/L2/L3/PE • Ethernet/Antenna port (with a waterproof cap) LAN/ANTENNA The SCB3000 is installed in places where there is no significant shaking, shock or vibration, and not subject to rain or snow.
• To ensure good heat dissipation and easy disassembly, the minimum clearance around the Horizontal Placement: 1. The SCB3000 can be placed horizontally, as shown in Figure 4.3-4. SCB3000 must not be less than the following values, as shown in Figure 4.2-2. 2.
4.5 Wiring Instructions 4.5.2 PLC Wiring Instructions (a) Protective Earth Wiring: The protective ground wire is connected to the PE of the base plate of inside the SCB3000 enclosure. (b) Remove the three-phase AC power line cover panel. (c) Connect the three-phase AC power line Note: Before connecting the AC power line, make sure that the switch upstream of SCB3000 is open.
4.6 Networking Diagrams 4.5.4 Description of LAN communication wiring The SCB3000 can be connected to routers, computers, switches and other equipment through the network cable; The network cable is connected to the internal NET port of the SCB3000; if you select Standalone the fiber optic version of this device, the network cable can be connected to the TP1 or TP2 port (the NET port has been connected to the TP3 port for the fiber optic version of this device).
5 System Operations 5.2 Master Computer Operations & Parameter Configurations ProMate is a software released by us for the configuration of the SCB3000 functions, it 5.1 Indicator Description enables the modification of the network IP address of the SCB3000, the configuration of the number of port-connected inverters, time settings, RCR and DRED feature configuration, field debugging and more.
Page 9
2. SCB3000 static IP address connection: (d) In the local connection popup dialog box, right-click "Local connection" and click "Properties". Note: SCB3000 is set to dynamic IP mode by default, you need to switch the SCB3000 to static IP mode first by pressing and holding the "RELOAD"...
Page 10
Modbus protocol for communications after all parameters have been configured. Note: If there is only one Box-type substation on the customer site, and the data is uploaded to GOODWE servers, there is no need to configure the box number and address through ProMate, simply connect ProMate, click to get the inverter list to see if the inverter is all online.
Page 11
(b) Settings of Device Count and Box No (c) Inverter Address Configuration Connecting the SCB3000 to the inverter requires the Modbus address to be configured, Enter numbers for both "Device Count" and "Box No". with the option of one click and manual operation available for the inverter address For "Device Count", enter the number of inverters actually connected to the current SCB3000.
Page 12
(d) Manually configure the inverter address As shown below: Click the "Update" button, enter the parameters to be modified in the As shown below: If there are special requirements for the inverter address on the customer popup dialog box, click "OK" and then click "Manual config". site, you can choose to manually add the Modbus address by clicking "Add", entering the inverter serial number, box number, and the corresponding Modbus address in the following popup box, selecting "OK", and then clicking "Manual config"...
Do not power off during the program upgrade. 6.2 Remote Upgrade The upgrade program is uploaded to the server by GOODWE in the background, and the SCB3000 will detect the upgrade by itself.
Transmission distance 20KM The power adapter is faulty Replace the power adapter Fiber Parameters Interface Contact the supplier or GOODWE A port: 1550nm(Transmit) 1310nm( Receive) The SCB3000 system failure Optical Ports Services B port: 1310nm(Transmit) 1550nm(Receive) Check the three-phase AC power line is Size(L*W*H) 351×460×142.2mm...