Forced Cooling Operation

2. Forced Cooling Operation

Outline
The forced cooling operation is allowed when both the following conditions are met.
1. The outdoor unit is not abnormal and not in the 3-minute standby mode.
2. The outdoor unit is not operating.
Protection functions have priority over all other functions during forced cooling operation.
Details
 With Wired Remote Controller (BRC1E73)
1. Set to COOL operation using the remote
2. Press and hold Cancel button for 4 seconds
3. Select
4. Press On/Off button within 10 seconds, and
 Forced cooling operation will stop
 With Wireless Remote Controller (BRC082A43)
1. Press
2. Press
3. Press
 Forced cooling operation will stop
119
controller.
or longer. Service settings menu is
displayed.
Test Operation
in the service
settings menu, and press Menu/OK button.
Basic screen returns and "Test Operation"
is displayed at the bottom.
the forced cooling operation starts.
automatically after about 15 minutes.
To stop the operation, press On/Off button.
button and select the COOL
operation.
button twice. "TEST" is
displayed.
button within 10 seconds, and
the forced cooling operation starts.
automatically after about 15 minutes.
To stop the operation, press
Basic screen
1.
2.
Service Settings
menu screen
3.
4.
button.
SiUS071735EB
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Press On/Off button
(within 10 seconds).
Trial Operation and Field Settings