Safety Information; Construction; Displays; Description - GEM 1441 cPos-X Operating Instructions Manual

Intelligent electro-pneumatic positioner
Hide thumbs Also See for 1441 cPos-X:
Table of Contents

Advertisement

3 Safety information

3 Safety information
The safety information in this document refers only to an indi-
vidual product. Potentially dangerous conditions can arise in
combination with other plant components, which need to be
considered on the basis of a risk analysis. The operator is re-
sponsible for the production of the risk analysis and for com-
pliance with the resulting precautionary measures and re-
gional safety regulations.
The document contains fundamental safety information that
must be observed during commissioning, operation and main-
tenance. Non-compliance with these instructions may cause:
- Personal hazard due to electrical, mechanical and chemical
effects.
- Hazard to nearby equipment.
- Failure of important functions.
- Hazard to the environment due to the leakage of dangerous
materials.
The safety information does not take into account:
- Unexpected incidents and events, which may occur during
installation, operation and maintenance.
- Local safety regulations which must be adhered to by the
operator and by any additional installation personnel.
Prior to commissioning:
1. Transport and store the product correctly.
2. Do not paint the bolts and plastic parts of the product.
3. Carry out installation and commissioning using trained
personnel.
4. Provide adequate training for installation and operating
personnel.
5. Ensure that the contents of the document have been fully
understood by the responsible personnel.
6. Define the areas of responsibility.
7. Observe the safety data sheets.
8. Observe the safety regulations for the media used.
During operation:
9. Keep this document available at the place of use.
10. Observe the safety information.
11. Operate the product in accordance with this document.
12. Operate the product in accordance with the specifications.
13. Maintain the product correctly.
14. Do not carry out any maintenance work and repairs not de-
scribed in this document without consulting the manufac-
turer first.
In cases of uncertainty:
15. Consult the nearest GEMÜ sales office.
4 Product description

4.1 Construction

GEMÜ 1441 cPos-X
Item
Name
1
Housing cover
2
Inspection glass
3
Housing base
4
Pneumatic panel
C
Conexo

4.2 Displays

4.2.1 Status display
The status display shows the most important operating in-
formation for the product. Display state:
- Off – the product is not ready for operation (switched off or
defective)
- On – the product is ready for operation
- Starting... – the product is starting (lasts for approx. 20
seconds)

4.3 Description

The GEMÜ 1441 cPos-X is an intelligent, digital electro-pneu-
matic positioner in 2-wire technology used to control pneu-
matically operated process valves. It can be combined with
single acting or double acting linear actuators or quarter turn
actuators. This means that it can be used, among other
things, for diaphragm, globe and diaphragm globe valves as
well as for ball valves and butterfly valves, for instance. The
positioner has a robust housing with a covered LCD display
for status information. The positioner can be operated re-
motely using a mobile device in order to configure settings
and to view detailed information.

4.4 Function

The GEMÜ 1441 digital electro-pneumatic positioner is an in-
telligent digital positioner designed for mounting to pneu-
matic actuators. The product is directly mounted on the actu-
ator as standard. The travel sensor is already integrated in the
positioner. As an option, the product can be ordered for a re-
mote mounting type, in which a separate travel sensor is con-
nected using an M12 connector. The travel sensor measures
the current position of the valve and reports it to the product's
6 / 33
1
2
3
4
C
Materials
Grivory PA 6.6
PC
Grivory PA 6.6
Grivory PA 6.6
www.gemu-group.com

Advertisement

Table of Contents
loading

Table of Contents