Toshiba MMK-UP0271HP Series Service Manual page 143

Table of Contents

Advertisement

Table 1.Setting data(CODE No. table(example))
DN
Filter display delay timer
01
Dirty state of filter
02
Central control address
03
Specific indoor unit priority
04
Heating suction temperature shift
06
Automatic mode
0D
Cooling only
0F
Type
10
Indoor unit capacity
11
Line address
12
Indoor unit address
13
Group address
14
Flap type (Wind direction adjustment)
19
Temperature range of cooling/heating
1E
automatic SW control point
Automatic restart of power failure
28
Humidifier operation condition
29
Selection of option / Trouble input
2A
(TCB-PCUC2E: CN3)
HA terminal (CN61) select
2E
Ventilating fan control
31
Sensor SW
32
Temperature unit select
33
External static pressure
5D
Timer setting (wired remote controller)
60
7A
Remote controller operation save function
D0
E0
Region
Presence of Application control kit
F6
(TCB-PCUC2E)
FC
Communication protocol
FE
FS unit adress
Remote controller setting
103
1Fb
Remote controller operation
1FC
Indoor Unit terminating resistance
Table 2. Type : CODE No.10
Setting
Type
data
*1
4-way Air Discharge
0001
Cassette Type
0008
High wall type
1 *
EEPROM initial value on the P.C. board for indoor unit
servicing.
2 *
CAUTION
< Model name MMK-UP****HP-E(TR) >
For the above model. Set the CODE no. to
"E0"
the setting data "0000" (initial) to "0004"
Item
Type name abb.
MMU-UP****HP-E(TR)
MMK-UP****HP-E(TR)
Setting data
0004 : Global model
Table 3. Indoor unit capacity : CODE No.11
Setup data
Model
*1
0000
Invalid
0012
027 type
0013
030 type
0015
036 type
- 143 -
Factory-set value
0002 : 2500H
0000 : Standard
00Un/0099 : Unfixed
0000 : No priority
0001 : No automatic
0000 : Heat pump
Depending on model type
According to capacity type
00Un/0099 : Unfixed
00Un/0099 : Unfixed
00Un/0099 : Unfixed
Depending on Type
0000 : None
0000 : Usual
0002 : None
0000 : Usual (HA terminal)
0000 : Unavailable
0000 : Body sensor
0000 : Default setting
0000 : Available
0001 : Enable
0000 : Japan model
0000 : None
0000 : TCC-LINK
00Un/0099 : Unfixed
0000 : With remote controller
0000 : Operation possible
0000 : OFF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmk- up0301hp seriesMmk-up0361hp series