Toshiba MMK-UP0271HP Series Service Manual page 137

Table of Contents

Advertisement

No.
Part name
1)
10
Cross flow fan
2)
3)
4)
5)
Procedures
Follow the procedure item 3 , 7 and 8 .
Loosen the set screw of the cross flow fan.
(Refer to the 9 for how to remove set screw.)
Remove 4 fixing screws from the bearing base
then remove it from the main unit.
Remove 4 screws which are fixing heat
exchanger.
Lift up the heat exchanger follow the figure.
Pull out the left hand side until the cross flow
fan is released from the shaft of the fan motor
and then pull out the lower side of heat
exchanger follow the figure.
<To re-installation>
To incorporate the fan motor and the
1)
motor into the position in the following
figure.
Install the cross flow fan so that the right
-
end of the 1st joint from the right of the
Cross flow fan is keep 4.0mm from closed
wall of the main unit.
4 mm
Cross flow fan
Holding the set screw, install the
-
cross flow fan so that thin area on shaft of
the fan motor comes to the mounting hole
of the set screw.
Body back
Fan motor
- 137 -
Remarks
Heat exchanger
Cross flow fan
Bearing base
Screw
Heat exchanger
Cross flow fan
Screw