Adjustment of air direction
1. Using the remote controller switch, change the
up/down air direction by moving the horizontal
louver.
2. Adjust the right/left air direction by bending the
vertical grille inside of the air outlet port with
hands.
REQUIREMENT
Do not touch the horizontal louver directly with
hands; otherwise a trouble may be caused.
For handling of the horizontal louver, refer to
"Owner's Manual" attached to the outdoor unit.
Group control
• In a group control a remote controller can
control up to maximum 8 or 16 units.
(Depending on the outdoor unit.). The wired
remote controller only can control a group
control. The wireless remote controller is
unavailable for this control.
• For cabling procedure and cables of the
individual line (Identical refrigerant line) system,
refer to "Electrical connection" in this Manual.
• Cabling between indoor units in a group is
performed in the following procedure. Connect
the indoor units by connecting the remote
controller inter-unit cables from the remote
controller terminal blocks (A, B) of the indoor
unit connected with a remote controller to the
remote controller terminal blocks (A, B) of the
other indoor unit. (Non-polarity)
• For address setup, refer to the Installation
Manual attached to the outdoor unit.
NOTE
Network adapter (Model TCB-PCNT20E) can not
connect to this High Wall type air conditioner.