Wiring And Connection; Cable Gland And Transmission Cable (Crimp Terminal) - Nagano Keiki EJ15 User Manual

Intrinsically safe pressure sensor for high pressure hydrogen application
Table of Contents

Advertisement

Cable
< Fig. 6-3 Recommended mounting direction for possible water spraying >

7. WIRING AND CONNECTION

■ 7.1 Cable Gland and Transmission Cable (crimp terminal) for Terminal
Box Type
Cable glands, cables and crimp terminals (round type) are not supplied with this product
(for terminal box type) and need to be prepared according to the following cable outlet
specifications.
Model
Cable
No.
outlet size
JIS F 8801
EJ15
Type B,
G1/2
7.1.1 Prepare a cable gland that conforms to the specifications of the cable outlet (JIS
F 8801 Type B G1/2) and conforms to IP65 or higher. Select a cable gland made
of metal in accordance with intrinsically safe requirements.
7.1.2
Transmission cable to be used between the terminal box sensor and safety
barrier should have two or more cores (or a shielded wire if grounding from the
pipe (EJ15 body) is unavailable), outside diameter matching the cable gland size,
and the lead wire with a conductor cross-sectional area (core wire) matching the
crimp terminal. The cable should also matches withstanding voltage between
cable conductors (core wires) and between the conductor and ground.
Moreover, use the cable that has less allowable parameters (see "3.2 Intrinsically
Safe Specifications") than those provided as external wiring of Intrinsically Safe
Circuits (will vary depending on your safety barrier).
Size of terminal block screws
(Conductor cross-sectional
Compatible
area of crimp terminal
cable dia. (mm)
Conductor cross-sectional
area of the crimp terminal)
According to
cable gland
specifications
< Table 7-1 >
Top
Cable outlet
Cable gland
Bottom
M3.5
2
(0.5 to 1.25mm
)
based on JIS C 2805
15
Withstand voltage
(V AC) 1 minute
(conductor to ground)
500
TY-EJ15-003A Rev.2

Advertisement

Table of Contents
loading