Electrical Safety In Installation, Start-Up And Maintenance - ABB ACS580-0P Supplement Installation Manual

Enclosed drives (230v, 1-100 hp; 480v, 1-200 hp; 575, 2-150 hp)
Hide thumbs Also See for ACS580-0P:
Table of Contents

Advertisement

Supplemental Installation Manual for ACS580-0P
• Before you connect voltage to the drive,
make sure that the drive covers are on.
Keep the covers on during the operation.
• Before you adjust the drive operation limits,
make sure that the motor and all driven
equipment can operate throughout the set
operation limits.
• Before you activate the automatic fault reset
or automatic restart functions of the drive
control program, make sure that no
dangerous situations can occur. These
functions reset the drive automatically and
continue operation after a fault or supply
break. If these functions are activated, the
installation must be clearly marked as
defined in IEC/EN 61800-5-1, subclause
6.5.3, for example, "THIS MACHINE
STARTS AUTOMATICALLY".
• The maximum number of drive power-ups is
five in ten minutes. Too frequent power-ups
can damage the charging circuit of the DC
capacitors.
• If you have connected safety circuits to the
drive (for example, emergency stop and
Safe torque off), validate them at the start
up. For the validation of the Safe Torque Off,
see
ACS580 firmware manual
(3AXD50000016097 [English]).
validation of other safety circuits, see the
instructions provided with them.
Note:
• If you select an external source for start
command and it is on, and the start
command is level-triggered, the drive will
start immediately after fault reset. See
parameters 20.02 Ext1 start trigger type and
20.07 Ext2 start trigger type in
firmware manual (3AXD50000016097
[English]).
• When the control location is not set to Local
(text Hand is not shown on the top row of the
panel and parameter 19.19 Off mode
disable has value Off button disabled), the
stop key on the control panel will not stop
the drive.
• Frames R1...R5: Do not attempt to repair a
• Frames R6...R9: Can be repaired by
Electrical safety in installation,
start-up and maintenance
Precautions before electrical work
These warnings are for all personnel who do
work on the drive, motor cable or motor.
injury or death, or damage to the equipment
can occur. If you are not a qualified electrical
professional, do not do electrical installation or
maintenance work. Go through these steps
before you begin any installation or
maintenance work.
1. Clearly identify the work location.
2. Disconnect all possible voltage sources.
For the
ACS580
3. Protect any other energized parts in the
4. Take special precautions when close to bare
5. Measure that the installation is
malfunctioning drive; contact your local
representative for replacement or repair by
authorized persons.
authorized persons.
WARNING! Frames R1 ... R9: Obey
these instructions. If you ignore them,
Lock and tag.
• Open the main disconnector at the power
supply of the drive.
• Make sure that reconnection is not
possible.
• Disconnect any external power sources
from the control circuits
• After you disconnect the drive, always
wait for 5 minutes to let the intermediate
circuit capacitors discharge before you
continue.
work location against contact.
conductors.
de-energized.
• Use a multimeter with an impedance of at
least 1 Mohm.
5
Safety instructions