Supplemental Installation Manual for ACS580-0P
575 Volt
Type Code
ACS580-0P-02A7-6
ACS580-0P-03A9-6
ACS580-0P-06A1-6
ACS580-0P-09A0-6
ACS580-0P-011A-6
ACS580-0P-017A-6
ACS580-0P-022A-6
ACS580-0P-027A-6
ACS580-0P-032A-6
ACS580-0P-041A-6
ACS580-0P-052A-6
ACS580-0P-062A-6
ACS580-0P-077A-6
ACS580-0P-099A-6
ACS580-0P-125A-6
ACS580-0P-144A-6
1)
"0P" represents a disconnect with fuses. 0P+F255 represents a circuit breaker.
2)
0P+F255 is rated 600Y/347V unless otherwise specified. For use on solidly grounded Wye source only.
3)
0P+F255 supports Delta network configuration.
4)
Only available for packaged drives in box enclosures.
Branch circuit protection
Input power is connected to the ACS580 through a door interlocked disconnect
switch or circuit breaker. When connected to a 240V or 480V power source, the
ACS580 with the circuit breaker option is suitable for use on a circuit capable of
delivering not more than 100,000 RMS symmetrical amperes. When connected to a
600V power source, F255 configurations are suitable for use on a circuit capable of
delivering not more than 10,000 RMS symmetrical amperes (75-150 HP), and not
more than 25,000 RMS symmetrical amperes (2-60 HP).
Fuses
Note: The UL listed drive fuses in the table are provided in the purchased product.
• Replacement fuses are required to be of the same class, current rating, and
voltage rating. Fuses from other manufacturers can be used if they are 600V rated
and meet the specifications given in the table.
• Fuses with higher current rating than specified must not be used.
Output Ratings
1, 2
A
HP
2.7
2
3.9
3
6.1
5
9
7.5
11
10
17
15
22
20
27
25
32
30
41
40
3
52
50
62
60
77
75
99
100
125
125
144
150
Base
Maximum Power Wiring Data
Drive
Circuit
Circuit
Frame
Breaker
Breaker
Size
(+F255)
UL
UL
(NEMA)
4
(NEMA)
Type 3R
Type 1
and 12
R2
#10
#10
62 in-lbs
62 in-lbs
R2
#12
#12
62 in-lbs
62 in-lbs
R2
#10
#10
62 in-lbs
62 in-lbs
R2
R2
R2
#6
#6
62 in-lbs
62 in-lbs
R3
R3
#4
#4
62 in-lbs
62 in-lbs
R3
R5
#3
Consult
Factory
62 in-lbs
R5
#2
62 in-lbs
R6
#1
62 in-lbs
R6
#1/0
62 in-lbs
R7
#3/0
124 in-lbs
R7
250 MCM
124 in-lbs
R8
Disconne
Disconne
Motor
ct Switch
ct Switch
Terminals
UL
UL
(NEMA)
(NEMA)
4
Type 1
Type 3R
and 12
#10
#10
#6
55 in-lbs
55 in-lbs
1.1 ft-lbs
#6
#6
55 in-lbs
55 in-lbs
#2
2.6 ft-lbs
#4
#4
55 in-lbs
55 in-lbs
#3
Consult
#2/0
Factory
55 in-lbs
4.1 ft-lbs
#2
55 in-lbs
#1
300 MCM
275 in-lbs
29.5 ft-lbs
#1/0
275 in-lbs
#3/0
500 MCM
275 in-lbs
29.5 ft.lbs
250 MCM
275 in-lbs
300 MCM
2 x 300
MCM
275 in-lbs
29.6 ft-lbs
ACS580-0P
17
Ground
Lugs UL
(NEMA)
Type 1
and 12
#2
50 in-lbs
3 x #3/0
250 in-lbs

Advertisement

Table of Contents
loading